The performance of a desiccant wheel air conditioning system with high-temperature chilled water from natural cold source

被引:42
作者
Chen, Liu [1 ]
Tan, Yikun [1 ]
机构
[1] Xian Univ Sci & Technol, Energy Sch, Yanta Rd, Xian 710054, Shaanxi, Peoples R China
基金
中国国家自然科学基金;
关键词
Air-conditioning system; Desiccant wheel; High-temperature chilled water; Surface air-cooler; Natural cold source; MATHEMATICAL-MODEL; EXERGY ANALYSIS; COOLING SYSTEM; SILICA-GEL; HEAT-PUMP; DRIVEN; DEHUMIDIFICATION; HOT;
D O I
10.1016/j.renene.2019.08.082
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A novel desiccant wheel air conditioning system that uses high-temperature chilled water from natural cold source (DWACS + HCW) is proposed. The proposed system integrates the renewable regeneration heat source and natural cold source, which are beneficial for energy saving. A model of the proposed system was developed, and the main components and the overall model were experimentally validated. The performance and the effects of the important parameters of the system under high humidity (32 degrees C, 80% RH), moderate humidity (32 degrees C, 60% RH) and low humidity (32 degrees C, 40% RH) conditions was studied numerically. The results showed that the system could achieve the supply air to the required temperature and humidity ratio in high, moderate and low humidity conditions, and compared to conventional solar desiccant wheel air conditioning systems (SDWACS), the energy performance is more efficient mainly due to high cooling and dehumidification capacity of surface air-cooler with high temperature chilled water. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2142 / 2157
页数:16
相关论文
共 45 条
[11]   Desiccant cooling air conditioning: a review [J].
Daou, K ;
Wang, RZ ;
Xia, ZZ .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2006, 10 (02) :55-77
[12]   Experimental and theoretical investigation of thermal performance of underground cold-water reservoirs [J].
Dehghan, A. A. ;
Dehghani, A. R. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (05) :816-824
[13]   Operational experiences with solar air collector driven desiccant cooling systems [J].
Eicker, Ursula ;
Schneider, Dietrich ;
Schumacher, Juergen ;
Ge, Tianshu ;
Dai, Yanjun .
APPLIED ENERGY, 2010, 87 (12) :3735-3747
[14]   A mathematical model for predicting the performance of the solar energy assisted hybrid air conditioning system, with one-rotor six-stage rotary desiccant cooling system [J].
Elzahzby, Ali M. ;
Kabeel, A. E. ;
Bassuoni, M. M. ;
Abdelgaied, Mohamed .
ENERGY CONVERSION AND MANAGEMENT, 2014, 77 :129-142
[15]   Performance of solar-desiccant cooling system with Silica-Gel (SiO2) and Titanium Dioxide (TiO2) desiccant wheel applied in East Asian climates [J].
Enteria, Napoleon ;
Yoshino, Hiroshi ;
Mochida, Akashi ;
Satake, Akira ;
Yoshie, Ryuichiro ;
Takaki, Rie ;
Yonekura, Hiroshi ;
Mitamura, Teruaki ;
Tanaka, Yasumitsu .
SOLAR ENERGY, 2012, 86 (05) :1261-1279
[16]   Ground heat exchangers: Applications, technology integration and potentials for zero energy buildings [J].
Gao, Jiajia ;
Li, Anbang ;
Xu, Xinhua ;
Gang, Wenjie ;
Yan, Tian .
RENEWABLE ENERGY, 2018, 128 :337-349
[17]   A review of the mathematical models for predicting rotary desiccant wheel [J].
Ge, T. S. ;
Li, Y. ;
Wang, R. Z. ;
Dai, Y. J. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2008, 12 (06) :1485-1528
[18]   Review on solar powered rotary desiccant wheel cooling system [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 39 :476-497
[19]   A mathematical model for predicting the performance of a compound desiccant wheel (A model of compound desiccant wheel) [J].
Ge, T. S. ;
Ziegler, F. ;
Wang, R. Z. .
APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) :1005-1015
[20]   Performance comparison between a solar driven rotary desiccant cooling system and conventional vapor compression system (performance study of desiccant cooling) [J].
Ge, T. S. ;
Ziegler, F. ;
Wang, R. Z. ;
Wang, H. .
APPLIED THERMAL ENGINEERING, 2010, 30 (6-7) :724-731