Induction Voltage Regulator Performance in Primary Distribution Networks With a High Degree of Distributed Generation

被引:6
作者
Matsumoto, Thomas R. [1 ]
Nabeta, Silvio I. [1 ]
Chabu, Ivan E. [1 ]
Nagao, Shigueru [1 ]
Santos, Nerivaldo R. [2 ]
Dominice, Alexandre [2 ]
机构
[1] Univ Sao Paulo, Dept Elect Energy & Automat, Polytech Sch, BR-05508010 Sao Paulo, Brazil
[2] EDP Sao Paulo, BR-08820460 Mogi Das Cruzes, SP, Brazil
关键词
Voltage control; Regulators; Distributed power generation; Photovoltaic systems; Windings; On load tap changers; Voltage Control; Distributed Power Generation; Induction Voltage Regulator; Distribution Network; PENETRATION; PROFILE;
D O I
10.1109/TPWRD.2020.3015927
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The main purpose of this paper is to study and evaluate the use of induction voltage regulators in distribution networks with several sources of renewable distributed generation. Because this type of generation is not steady and is dependent on weather conditions, such as wind and solar irradiation, the voltage at several points of a network may exhibit significant variation. Therefore, conventional voltage regulators will be subject to a larger number of tap changes, which shorten their useful lifetime. In this context, an induction voltage regulator, which has not been explored in the literature, is an alternative that can overcome this problem, since it can maintain a constant voltage level in the output without its components wearing out.
引用
收藏
页码:1837 / 1846
页数:10
相关论文
共 37 条
[1]   Optimal Placement and Sizing of Distributed Generation and Capacitor Banks in Distribution Systems Using Water Cycle Algorithm [J].
Abou El-Ela, Adel A. ;
El-Sehiemy, Ragab A. ;
Abbas, Ahmed Samir .
IEEE SYSTEMS JOURNAL, 2018, 12 (04) :3629-3636
[2]   Distribution Voltage Control Considering the Impact of PV Generation on Tap Changers and Autonomous Regulators [J].
Agalgaonkar, Yashodhan P. ;
Pal, Bikash C. ;
Jabr, Rabih A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (01) :182-192
[3]  
ANEEL-Agencia Nacional de Energia Eletrica, 2006, EST VID UT EC TAX DE
[4]  
[Anonymous], 2000, P C REC IEEE IND APP
[5]  
Ari GK., 2011, Clean Electrical Power (ICCEP), 2011 International Conference on, P744, DOI DOI 10.1109/ICCEP.2011.6036386
[6]   STATIC ALTERNATIVE TO THE TRANSFORMER ON-LOAD TAP-CHANGER [J].
ARRILLAGA, J ;
DUKE, RM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01) :86-91
[7]  
Ayres W. E. M., 1931, J I ELECT ENG, V69, P1208
[8]  
Bala S, 2012, IEEE ENER CONV, P4061, DOI 10.1109/ECCE.2012.6342271
[9]   Combined Effect of CVR and DG Penetration in the Voltage Profile of Low-Voltage Secondary Distribution Networks [J].
Bokhari, Abdullah ;
Raza, Ashhar ;
Diaz-Aguilo, Marc ;
de Leon, Francisco ;
Czarkowski, Dariusz ;
Uosef, Resk Ebrahem ;
Wang, David .
IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (01) :286-293
[10]  
Boveri Asea Brown, 2012, CONNECTION DIAGRAM U