Feasibility study on the low temperature district heating and cooling system with bi-lateral heat trades model

被引:19
作者
Im, Yong-Hoon [1 ]
Liu, Jie [2 ]
机构
[1] Korea Inst Energy Res, Daejeon, South Korea
[2] Yeungnam Univ, Sch Mech Engn, Gyongsan, Gyeongbuk, South Korea
关键词
Low temperature district heating; Bi-lateral heat trades model; Combined cooling; Heating and power; Simulation; OPTIMAL-DESIGN; OPERATION; NETWORK; POWER; OPTIMIZATION; BUILDINGS;
D O I
10.1016/j.energy.2018.04.094
中图分类号
O414.1 [热力学];
学科分类号
摘要
A Novel low temperature district heating and cooling system with auxiliary heat storage pipe system is proposed for reflecting new features of bi-lateral energy trades effectively in emerging energy prosumer based new energy business platform. The newly proposed district heating and cooling system can provide more favorable operating conditions to implement bi-lateral heat trades system between the heat supplier and the prosumers, who operating their own distributed energy generation unit such as a cogeneration etc., connected to the network being able to utilize low-exergy level of waste heats available in consumer side. In this study, the appropriate system configuration for reliable operation, the optimal operation rules, the functionality of auxiliary heat storage pipe on bi-lateral heat trades and its operating characteristics etc. are analyzed extensively by developing simplified simulation models of the DHC network using Matlab/Simulink without any support by experiment or field measurement. The simulation results show that the newly suggested low temperature DHC system with auxiliary heat storage pipe can add improved rooms of operating flexibility to maintain stable supplying temperature conditions and is superior to conventional system in handling bi-lateral heat trades model. It is also shown that the new concept of DHC system can alleviate the inefficiency arising from mismatching of heat demand and supply in consumer side significantly, not to mention of the heat losses during the operation. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:988 / 999
页数:12
相关论文
共 25 条
[1]   Optimal design and operation of district heating and cooling networks with CCHP systems in a residential complex [J].
Ameri, Mohammad ;
Besharati, Zahed .
ENERGY AND BUILDINGS, 2016, 110 :135-148
[2]   A feasibility and performance assessment of a low temperature district heating system - A North Japanese case study [J].
Baldvinsson, Ivar ;
Nakata, Toshihiko .
ENERGY, 2016, 95 :155-174
[3]   An optimization approach for district heating strategic network design [J].
Bordin, Chiara ;
Gordini, Angelo ;
Vigo, Daniele .
EUROPEAN JOURNAL OF OPERATIONAL RESEARCH, 2016, 252 (01) :296-307
[4]   Optimal operating strategies of combined cooling, heating and power systems: A case study for an engine manufacturing facility [J].
Calise, Francesco ;
d'Accadia, Massimo Dentice ;
Libertini, Luigi ;
Quiriti, Edoardo ;
Vanoli, Raffaele ;
Vicidomini, Maria .
ENERGY CONVERSION AND MANAGEMENT, 2017, 149 :1066-1084
[5]   Combined cooling, heating and power: A review of performance improvement and optimization [J].
Cho, Heejin ;
Smith, Amanda D. ;
Mago, Pedro .
APPLIED ENERGY, 2014, 136 :168-185
[6]   Micro-CHP systems for residential applications [J].
De Paepe, Michel ;
D'Herdt, Peter ;
Mertens, David .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (18-19) :3435-3446
[7]   Assessment of absorption cooling as a district heating system strategy - A case study [J].
Fahlen, Elsa ;
Trygg, Louise ;
Ahlgren, Erik O. .
ENERGY CONVERSION AND MANAGEMENT, 2012, 60 :115-124
[8]   Modelling temperature dynamics of a district heating system in Naestved, Denmark - A case study [J].
Gabrielaitiene, Irina ;
Bohm, Benny ;
Sunden, Bengt .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (01) :78-86
[9]   Evaluation and sizing of a CCHP system for a commercial and office buildings [J].
Hanafizadeh, Pedram ;
Eshraghi, Javad ;
Ahmadi, Pouria ;
Sattari, Amirmohammad .
JOURNAL OF BUILDING ENGINEERING, 2016, 5 :67-78
[10]  
International Energy Agency (IEA), COMB HEAT POW