Study on VFTO of XiMeng UHV substation 1000kV GIS substation

被引:0
|
作者
Su, Xiu-Cheng [1 ]
Liu, Bo-Han [1 ]
Bo, Li [1 ]
Yan, Guo-Zeng [1 ]
Ni, Xiang-Ping [1 ]
Liu, Zhen-Tao [1 ]
机构
[1] State Grid AC Engn Construct Co, Beijing 102206, Peoples R China
关键词
UHV Substation; Transmission; GIS; VFTO; Insulator;
D O I
暂无
中图分类号
TP301 [理论、方法];
学科分类号
081202 ;
摘要
This paper presents the VFTO calculation and analyzing results of XiMeng UHV pilot project in China. The result shows that the maximum voltage amplitude of VFTO in GIS is 1981kV, so that the pre-insert switching on off resistance is not necessary to installed on disconnector. In this case, it will reduce the probability of GIS failure operation and the potential supply current, and the safety and reliability of UHV GIS system will be improved. Meanwhile, the VFTO of a transformer in GIS substation is not high when the transformer is connected to GIS by overhead line.
引用
收藏
页码:335 / 341
页数:7
相关论文
共 50 条
  • [1] Study on VFTO of 1000 kV GIS substation
    Wuhan High Voltage Research Institute, SGCC, Wuhan 430074, China
    Gaodianya Jishu, 2007, 11 (27-32): : 27 - 32
  • [2] Electromagnetic Environment of 1000kV UHV AC Substation
    Wan, Bao-Quan
    Xie, Hui-Chun
    Zhang, Guang-Zhou
    Zhang, Xiao-Wu
    2010 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY & TECHNICAL EXHIBITION ON EMC RF/MICROWAVE MEASUREMENTS & INSTRUMENTATION, 2010, : 1413 - 1416
  • [3] Research on optimisation of minimum air clearance of 1000kV UHV AC substation
    Li Zhenqiang
    Xie Liang
    Liu Jing
    He Huiwen
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2687 - 2692
  • [4] Simulation research on VFTO waveform attenuation in UHV GIS substation
    Wang L.
    Liu Y.
    Feng Y.
    Wang H.
    Zhao J.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2019, 47 (22): : 45 - 51
  • [5] Simulation and Test Study on Very Fast Transient Overvoltage in 1000kV GIS Substation
    Han, Bin
    Lin, Jiming
    Ban, Liangeng
    Wang, Hao
    Li, Zhibing
    Xiang, Zutao
    2017 2ND ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2017), 2017, 199
  • [6] Wind load characteristics and effects of 1000kV UHV substation frame based on HFFB
    Tang, Hao
    Li, Fanghui
    Zhi, Xudong
    Zhao, Jie
    WIND AND STRUCTURES, 2024, 38 (06) : 477 - 492
  • [7] Diagnostic analysis and protective measures of transient ground potential rise in a 1000kv UHV substation
    Pang, Fubin
    Bu, Qiangsheng
    Liu, Yu
    Yuan, Yubo
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 1144 - 1148
  • [8] Simulation of VFTO Suppression Methods for 1100kV GIS Substation
    Gong, Wenxiu
    Wang, Peijin
    Li, Qingquan
    Xue, Weijian
    Qiao, Mu
    Wang, Xiao
    Pang, Yumei
    PROCEEDINGS OF 2019 IEEE 3RD INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC 2019), 2019, : 987 - 991
  • [9] Study on the impact of VFTO electromagnetic interference on electronic transformers in 500 kV GIS substation
    Wang, Jiaying (imwangjiaying@foxmail.com), 2016, China Machine Press (31):
  • [10] Measurement and simulation of disturbance voltage generated by VFTO in UHV GIS substation on the secondary cables
    Zhang, W. (zwd@ncepu.edu.cn), 1600, Chinese Society for Electrical Engineering (33):