Experimental study on R-410a evaporation heat transfer characteristics in oblong shell and plate heat exchanger

被引:34
作者
Kim, In-Kwan
Park, Jae-Hong
Kwon, Yong-Ha
Kim, Young-Soo
机构
[1] Pukyong Natl Univ, Dept Refrigerat & Air Conditioning Engn, Pusan 608739, South Korea
[2] Pukyong Natl Univ, Reg Res Ctr Adv Environm Friendly Energy Syst, Pusan, South Korea
关键词
D O I
10.1080/01457630701266454
中图分类号
O414.1 [热力学];
学科分类号
摘要
The evaporation heat transfer experiments were conducted with an oblong shell and plate heat exchanger without oil in the refrigerant loop using R-410A, a mixture of 50 wt% R-32 and 50 wt% R-125 that exhibits azeotropic behavior. An experimental refrigerant loop has been established to measure the evaporation heat transfer coefficient hr of R-410A in a vertical oblong shell and plate heat exchanger. Four vertical counter-flow channels were formed in the oblong shell and plate heat exchanger by four plates having a corrugated trapezoid shape of a 45 degrees. chevron angle. The upflow of the boiling R-410A in one channel receives heat from the hot downflow of water in the other channel. The effects of the refrigerant mass flux, average heat flux, refrigerant saturation temperature, and vapor quality of R-410A on the measured data were explored in detail. The results indicate that a rise in the refrigerant mass flux causes an increase in the hr. Raising the imposed wall heat flux was found to slightly improve hr. Finally, at a higher refrigerant saturation temperature, the hr is found to be lower. Based on the present data, an empirical correlation of the evaporation heat transfer coefficient was proposed.
引用
收藏
页码:633 / 639
页数:7
相关论文
共 9 条
[1]  
Akers W. W., 1958, Chem. Eng. Prog, V54, P89
[2]  
FARRELL P, 1991, 910197 SAE
[3]  
Kerner J., 1987, POWER, V131, P53
[4]  
Kline S.J., 1952, ASME Mechanical Engineering, V75, P3, DOI DOI 10.1016/J.CHAOS.2005.11.046
[5]  
LEE KB, 2003, J KOREAN SOC MARINE, V27, P108
[6]  
LEE KB, 2001, J KOREAN SOC MARINE, V25, P1220
[7]   Evaporation heat transfer and pressure drop characteristics of R-134a in the oblong shell and plate heat exchanger [J].
Park, JH ;
Kim, YS .
KSME INTERNATIONAL JOURNAL, 2004, 18 (12) :2284-2293
[8]  
SHAH RK, 1992, LECT SERIES, V1991
[9]   Designing control charts using an empirical reference distribution [J].
Willemain, TR ;
Runger, GC .
JOURNAL OF QUALITY TECHNOLOGY, 1996, 28 (01) :31-38