On-line corrosion monitoring in geothermal district heating systems. II. Localized corrosion

被引:25
|
作者
Richter, S.
Thorarinsdottir, R. I.
Jonsdottir, F.
机构
[1] Iceland Bldg Res Inst, IS-112 Reykjavik, Iceland
[2] Natl Energy Author, IS-108 Reykjavik, Iceland
[3] Univ Iceland, IS-101 Reykjavik, Iceland
关键词
steel; sulphide; geothermal; crevice corrosion;
D O I
10.1016/j.corsci.2006.10.030
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Corrosion monitoring in district heating systems has traditionally been performed by using off-line methods, such as weight loss. The disadvantage is that the method is very slow, especially in low-corrosive environments, and that it only provides information about the past corrosion (accumulated over period of time). The purpose of the work is to test on-line monitoring methods in geothermal hot water in the district heating system in Reykjavik, Iceland. Geothermal water poses certain problems with regards to corrosion monitoring due to low conductivity, high pH and the presence of sulphide. These conditions make the geothermal environment low corrosive. However, a quality control is needed, especially since the sulphide causes the steel pipes to be more vulnerable towards localized corrosion. The methods used in this study were: linear polarization resistance (LPR), harmonic analysis (HA), electrochemical noise (EN) and zero resistance ammetry (ZRA). The Pitting Factor was measured with EN and showed promising results for measuring-localized corrosion on-line. A crevice corrosion cell also gave good results but had a low lifetime. However, the results of a galvanic corrosion cell (Fe/Cu) proved more difficult to interpret since they were dependent both on the dissolved oxygen and the sulphide level. (c) 2006 Published by Elsevier Ltd.
引用
收藏
页码:1907 / 1917
页数:11
相关论文
共 50 条
  • [1] On-line corrosion monitoring in geothermal district heating systems. I. General corrosion rates
    Richter, S.
    Hilbert, L. R.
    Thorarinsdottir, R. I.
    CORROSION SCIENCE, 2006, 48 (07) : 1770 - 1778
  • [2] On-line corrosion monitoring in geothermal steam pipelines
    Inman, ME
    Sharp, RM
    Wilson, PT
    Wright, GA
    GEOTHERMICS, 1998, 27 (02) : 167 - 182
  • [3] CORROSION IN SOLAR HEATING SYSTEMS. II. CORROSION BEHAVIOUR OF AA 6351 IN WATER/GLYCOL SOLUTIONS.
    Monticelli, C.
    Brunoro, G.
    Trabanelli, G.
    Frignani, A.
    Werkstoffe und Korrosion, 1987, 38 (02): : 83 - 88
  • [4] ON-LINE CORROSION MONITORING
    BOVANKOVICH, JC
    MATERIALS PROTECTION AND PERFORMANCE, 1973, 12 (06): : 20 - 23
  • [5] On-line corrosion monitoring services
    不详
    GEC JOURNAL OF TECHNOLOGY, 1997, 14 (02): : 124 - 124
  • [6] CORROSION PROBLEMS IN CENTRAL HEATING SYSTEMS.
    Davis, R.D.
    Anti-Corrosion Methods and Materials, 1987, 34 (09) : 6 - 11
  • [7] Monitoring and mitigating corrosion in geothermal systems
    Schott, Tiphaine
    Liautaud, Francoise
    MATERIALS AND CORROSION-WERKSTOFFE UND KORROSION, 2022, 73 (12): : 1916 - 1942
  • [8] Testing corrosion rates on steel piping in geothermal district heating
    Ince, Umut
    Toksoy, Macit
    Guden, Mustafa
    MATERIALS PERFORMANCE, 2008, 47 (05) : 56 - 59
  • [9] Reliability of on-line corrosion monitoring system
    Xiang, Min
    Li, Chang-Jun
    Liao, Ke-Xi
    Yang, Yi
    Xinan Shiyou Daxue Xuebao/Journal of Southwest Petroleum University, 2007, 29 (03): : 157 - 159
  • [10] Monitoring corrosion on-line with fiber optics
    不详
    EPRI JOURNAL, 1997, 22 (06): : 5 - 5