Design and analysis of tilt integral derivative controller with filter for load frequency control of multi-area interconnected power systems

被引:141
作者
Sahu, Rabindra Kumar [1 ]
Panda, Sidhartha [1 ]
Biswal, Ashutosh [1 ]
Sekhar, G. T. Chandra [1 ]
机构
[1] Veer Surendra Sai Univ Technol VSSUT, Dept Elect Engn, Burla 768018, Odisha, India
关键词
Load Frequency Control (LFC); Tilted Integral Derivative controller with; Filter (TIDF); Differential Evolution (DE) algorithm; Generation Rate Constraint (GRC); Governor Dead Band (GDB); Thyristor Controlled Series Compensator (TCSC); AUTOMATIC-GENERATION CONTROL; OF-THE-ART; PID CONTROLLER; ALGORITHM;
D O I
10.1016/j.isatra.2015.12.001
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this paper, a novel Tilt Integral Derivative controller with Filter (TIDF) is proposed for Load Frequency Control (LFC) of multi-area power systems. Initially, a two-area power system is considered and the parameters of the TIDF controller are optimized using Differential Evolution (DE) algorithm employing an Integral of Time multiplied Absolute Error (ITAE) criterion. The superiority of the proposed approach is demonstrated by comparing the results with some recently published heuristic approaches such as Firefly Algorithm (FA), Genetic Algorithm (GA) and Particle Swarm Optimization (PSO) optimized PID controllers for the same interconnected power system. Investigations reveal that proposed TIDF controllers provide better dynamic response compared to PID controller in terms of minimum undershoots and settling times of frequency as well as tie-line power deviations following a disturbance. The proposed approach is also extended to two widely used three area test systems considering nonlinearities such as Generation Rate Constraint (GRC) and Governor Dead Band (GDB). To improve the performance of the system, a Thyristor Controlled Series Compensator (TCSC) is also considered and the performance of TIDF controller in presence of TCSC is investigated. It is observed that system performance improves with the inclusion of TCSC. Finally, sensitivity analysis is carried out to test the robustness of the proposed controller by varying the system parameters, operating condition and load pattern. It is observed that the proposed controllers are robust and perform satisfactorily with variations in operating condition, system parameters and load pattern. (C) 2015 ISA. Published by Elsevier Ltd. All rights reserved.
引用
收藏
页码:251 / 264
页数:14
相关论文
共 36 条
  • [1] Ahamed TPI, 2002, ELECTR POW SYST RES, V63, P9, DOI 10.1016/S0378-7796(02)00088-3
  • [2] AI-Hamouz Z, 2011, ELECTR POW SYST RES, V81, P403
  • [3] Bacteria foraging optimization algorithm based load frequency controller for interconnected power system
    Ali, E. S.
    Abd-Elazim, S. M.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (03) : 633 - 638
  • [4] [Anonymous], J GLOBAL OPTIMIZATIO
  • [5] [Anonymous], 2000, Electric Energy Systems Theory-An Introduction
  • [6] [Anonymous], 2009, POWER SYSTEM STABILI
  • [7] Azar AT, 2015, STUD COMPUT INTELL, V575, pV
  • [8] Robust IMC-PID tuning for cascade control systems with gain and phase margin specifications
    Azar, Ahmad Taher
    Serrano, Fernando E.
    [J]. NEURAL COMPUTING & APPLICATIONS, 2014, 25 (05) : 983 - 995
  • [9] Azar AT, 2015, ADV COMPU INTELL ROB, P1, DOI 10.4018/978-1-4666-7248-2
  • [10] Load frequency control: a generalised neural network approach
    Chaturvedi, DK
    Satsangi, PS
    Kalra, PK
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1999, 21 (06) : 405 - 415