Mechanism of Saline Deposition and Surface Flashover on High-Voltage Insulators near Shoreline: Mathematical Models and Experimental Validations

被引:9
作者
Hussain, Muhammad Majid [1 ]
Chaudhary, Muhammad Akmal [2 ]
Razaq, Abdul [3 ]
机构
[1] Univ South Wales, Fac Comp Engn & Sci, Cardiff CF37 1DL, S Glam, Wales
[2] Ajman Univ, Dept Elect & Comp Engn, POB 346, Ajman, U Arab Emirates
[3] Abertay Univ, Sch Design & Informat, Dundee DD1 1HG, Scotland
关键词
saline mechanism; shoreline; wind speed; outdoor insulators; dry band arcing; flashover; ATMOSPHERIC CORROSION; MARINE AEROSOLS; COASTAL AREA; POLLUTION; PERFORMANCE; LINE;
D O I
10.3390/en12193685
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper deals with sea salt transportation and deposition mechanisms and discusses the serious issue of degradation of outdoor insulators resulting from various environmental stresses and severe saline contaminant accumulation near the shoreline. The deterioration rate of outdoor insulators near the shoreline depends on the concentration of saline in the atmosphere, the influence of wind speed on the production of saline water droplets, moisture diffusion and saline penetration on the insulator surface. This paper consists of three parts: first a model of saline transportation and deposition, as well as saline penetration and moisture diffusion on outdoor insulators, is presented; second, dry-band initiation and formation modelling and characterization under various types of contamination distribution are proposed; finally, modelling of dry-band arcing validated by experimental investigation was carried out. The tests were performed on a rectangular surface of silicone rubber specimens (12 cm x 4 cm x 8 cm). The visualization of the dry-band formation and arcing was performed by an infrared camera. The experimental results show that the surface strength and arc length mainly depend upon the leakage distance and contamination distribution. Therefore, the model can be used to investigate insulator flashover near coastal areas and for mitigating saline flashover incidents.
引用
收藏
页数:20
相关论文
共 32 条
[1]   Insulator Selection for AC Overhead Lines With Respect to Contamination [J].
Baker, A. C. ;
Farzaneh, M. ;
Gorur, R. S. ;
Gubanski, S. M. ;
Hill, R. J. ;
Karady, G. G. ;
Schneider, H. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1633-1641
[2]   CONTAMINATION PERFORMANCE OF HVDC STATION POST INSULATORS [J].
BAKER, AC ;
ZAFFANELLA, LE ;
ANZIVINO, LD ;
SCHNEIDER, HM ;
MORAN, JH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1968-1975
[3]   Effect of distance from sea on atmospheric corrosion rate [J].
Feliu, S ;
Morcillo, M ;
Chico, B .
CORROSION, 1999, 55 (09) :883-891
[4]   Dry deposition and concentration of marine aerosols in a coastal area, SW Sweden [J].
Gustafsson, MER ;
Franzen, LG .
ATMOSPHERIC ENVIRONMENT, 1996, 30 (06) :977-989
[5]  
Hamada S., 1986, FAC ENG YAMAGUCHI U, V01, P255
[6]  
Houlgate R.G., 1986, CIGRE PAP, V15, P12
[7]   Mechanism of Saline Deposition and Surface Flashover on Outdoor Insulators near Coastal Areas Part II: Impact of Various Environment Stresses [J].
Hussain, M. Majid ;
Farokhi, S. ;
McMeekin, S. G. ;
Farzaneh, M. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) :1068-1076
[8]  
Hussain MM, 2015, C ELECT INSUL DIEL P, P201, DOI 10.1109/CEIDP.2015.7352000
[9]   Risk Assessment of Failure of Outdoor High Voltage Polluted Insulators under Combined Stresses Near Shoreline [J].
Hussain, Muhammad Majid ;
Farokhi, Shahab ;
McMeekin, Scott G. ;
Farzaneh, Masoud .
ENERGIES, 2017, 10 (10)
[10]   FLASHOVER OF CONTAMINATED INSULATORS WITH CYLINDRICAL SYMMETRY UNDER DC CONDITIONS [J].
JOLLY, DC ;
POOLE, CD .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1979, 14 (02) :77-84