Power Quality Indices: A Saudi Steel Mill Case Study

被引:0
作者
El-Amin, Ibrahim M. [1 ]
Al-Elyani, Abdullah [1 ]
Shuaib, Abdelrahman [1 ]
机构
[1] King Fahd Univ Petr & Minerals, Dept Elect Engn, Dhahran, Saudi Arabia
来源
2013 INTERNATIONAL CONFERENCE ON COMPUTING, ELECTRICAL AND ELECTRONICS ENGINEERING (ICCEEE) | 2013年
关键词
Power Quality; Harmonic levels; Harmonic Standards; Arc furnace; Non-linear Loads; Point of Common Coupling (PCC); flicker; TRANSFORMERS; HARMONICS;
D O I
暂无
中图分类号
TP301 [理论、方法];
学科分类号
081202 ;
摘要
This paper presents results of field measurements of power quality indices at the terminals of an Electric Arc furnace connected at 34.5 kV to a 230 kV 60 Hz network in Saudi Arabia. The power quality indices that are measured are total harmonic distortion for voltage and current (THD V, THD I), individual harmonics, and flicker for short and long terms (P-st, P-lt). In addition, other electrical parameters are measured as well such as voltage (V-rms), current (I-rms), active power (P), reactive power (Q), power factor (PF), and frequency. All power quality parameters for both study cases are found to be within the IEEE and IEC standards. The installation of SVC and filters are mandatory. Long term Monitoring and country wide PQ study is recommended.
引用
收藏
页码:99 / 102
页数:4
相关论文
共 10 条