A permanent fault identification method for single-pole grounding fault of overhead transmission lines in VSC-HVDC grid based on fault line voltage

被引:20
作者
Li, Botong [1 ]
Cui, Hanqing [1 ]
Li, Bin [1 ]
Wen, Weijie [1 ]
Dai, Dongkang [2 ]
机构
[1] Tianjin Univ, Key Lab Smart Grid, Minist Educ, Sch Elect & Informat Engn, Tianjin 300072, Peoples R China
[2] State Grid Hebei Elect Power Corp Baoding Supply, Baoding 071000, Peoples R China
基金
国家重点研发计划;
关键词
Permanent fault identification; Hybrid DC circuit breaker; Overhead transmission lines; VSC-HVDC; PROTECTION;
D O I
10.1016/j.ijepes.2019.105603
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a permanent fault identification method for single-pole grounding fault of overhead transmission lines in VSC-HVDC grid based on fault line voltage is proposed. First, the working principle of the hybrid direct breaker circuit breaker (DCCB) and the discharge process of the internal capacitor of the hybrid DCCB are analyzed. Then, the transient processes of the fault line voltage under the conditions of permanent fault and transient fault are analyzed after reclosing the isolation switch of the DCCB on one side of the fault line. According to the difference of the fault line voltage under the conditions of permanent fault and transient fault, a permanent fault identification method for single-pole grounding fault of overhead transmission lines is proposed. The process of the identification will not affect the operating state of each converter in VSC-HVDC grid and it will not cause another fault impact to the system. Finally, a model of four-terminal VSC-HVDC system based on the modular multilevel converter (MMC) is built in PSCAD and the simulation results verify the feasibility and accuracy of this method.
引用
收藏
页数:9
相关论文
共 15 条
[1]  
Dennetiere Sebastien, 2015, 2015 IEEE Power & Energy Society General Meeting, P1, DOI 10.1109/PESGM.2015.7286153
[2]   Analysis on fault current limitation and self-recovery of MMC based on clamp double sub-module [J].
Ding, Yunzhi ;
Su, Jianhui ;
Zhou, Jian .
Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2014, 38 (01) :97-103
[3]   VSC-Based HVDC Power Transmission Systems: An Overview [J].
Flourentzou, Nikolas ;
Agelidis, Vassilios G. ;
Demetriades, Georgios D. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2009, 24 (3-4) :592-602
[4]   An intelligent algorithm for fault location on VSC-HVDC system [J].
Hao, Yongqi ;
Wang, Qian ;
Li, Yanan ;
Song, Wenfeng .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 94 :116-123
[5]   直流断路器技术发展综述 [J].
何俊佳 ;
袁召 ;
赵文婷 ;
方帅 ;
喻新林 ;
潘垣 .
南方电网技术, 2015, 9 (02) :9-15
[6]  
[李斌 Li Bin], 2018, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V38, P3727
[7]  
[李斌 Li Bin], 2017, [电力系统自动化, Automation of Electric Power Systems], V41, P77
[8]   Continuous Operation of Radial Multiterminal HVDC Systems Under DC Fault [J].
Li, Rui ;
Xu, Lie ;
Holliday, Derrick ;
Page, Frederick ;
Finney, Stephen J. ;
Williams, Barry W. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (01) :351-361
[9]  
[李笑倩 Li Xiaoqian], 2014, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V34, P6389
[10]   Protection of Nonpermanent Faults on DC Overhead Lines in MMC-Based HVDC Systems [J].
Li, Xiaoqian ;
Song, Qiang ;
Liu, Wenhua ;
Rao, Hong ;
Xu, Shukai ;
Li, Licheng .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (01) :483-490