摘要
Effects of water mal-distribution on thermostatic-expansion-valve (TEV) stability and its controlled two-circuit evaporator performance were investigated experimentally and numerically. 7 sets of water mal-distribution were obtained with Circuit 2 water percentage (F-2) from 36.9% to 9.1%. Results showed that the TEV control-loop was stable with F-2 from 36.9% to 27.0%, and the overall evaporator capacity decreased by 3.4%. However, hunting occurred with F-2 from 27.0% to 9.1% due to the evaporator outlet superheat smaller than the TEV minimal stable signal (MSS), hence system parameters such as evaporator pressures and temperatures oscillated over time. Hunting introduced a sharp decrease in the refrigerant flowrate to the evaporator, thus the overall evaporator capacity decreased by 14.1%. With water mal-distribution rate increased, the decrease in overall evaporator capacity was mainly attributed to Circuit 2 with smaller overall heat transfer coefficient. (C) 2014 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:38 / 47
页数:10
相关论文
共 28 条
[1]   Airflow maldistribution and the performance of a packaged air conditioning unit evaporator [J].
Aganda, AA ;
Coney, JER ;
Sheppard, CGW .
APPLIED THERMAL ENGINEERING, 2000, 20 (06) :515-528
[2]  
[Anonymous], 2004, 77252004 AQSIQ GBT
[3]   Experimental evaluation of electronic and thermostatic expansion valves performances using R22 and R407C [J].
Aprea, C ;
Mastrullo, R .
APPLIED THERMAL ENGINEERING, 2002, 22 (02) :205-218
[4]  
Blasius H., 1908, Z. Angew. Math. Phys., V56, P1
[5]   Thermostatic valve control using a non-azeotropic refrigerant, isobutane propane mixture [J].
Castle, TP ;
Richardson, RN ;
Ritter, TJ .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (04) :313-318
[6]   Experimental investigation of a minimum stable superheat. control system of an evaporator [J].
Chen, W ;
Chen, ZJ ;
Zhu, RQ ;
Wu, YZ .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (08) :1137-1142
[7]  
DITTUS F.W., 1930, Univ. California, V2, P443, DOI DOI 10.1016/0735-1933(85)90003-X
[8]  
DOMANSKI PA, 1991, ASHRAE TRAN, V97, P793
[9]  
Fagan T J., 1980, Transaction ASHREA, V86-2, P699
[10]   Dynamic characteristics of an air-to-water heat pump under frosting/defrosting conditions [J].
Huang, D. ;
He, Z. L. ;
Yuan, X. L. .
APPLIED THERMAL ENGINEERING, 2007, 27 (11-12) :1996-2002