Pressure measurements with valve-induced transient flow in water pipelines

被引:10
作者
Choi, Doo Yong [1 ]
Kim, Juhwan [1 ]
Lee, Doo-Jin [1 ]
Kim, Dohwan [1 ]
机构
[1] Korea Water Resources Corp, K Water Inst, Taejon 305730, South Korea
关键词
SCADA; water supply system; hydraulic transient; pressure measurement; transient analysis; valve-induced flow; NETWORK;
D O I
10.1080/1573062X.2013.832778
中图分类号
TV21 [水资源调查与水利规划];
学科分类号
081501 ;
摘要
Pressure measurements provide valuable insights for managing water supply systems by tracking time-dependent hydraulic transients. In this study, we report on two pressure-monitoring issues - sampling location and sampling interval - by analyzing a valve-induced transient event that was not recorded in the 1-min timestamp pressure generated by the existing supervisory control and data acquisition (SCADA) system of a real water transmission line in the southern part of Korea. Field measurement data show that the measured pressure magnitude is influenced by the sampling location, which depends on pipe connectivity and distance from automatic control valve, and by the sampling interval, which is sensitive to network size for wave propagation. Based on the findings of the field experiments, a pressure-measurement method is proposed by employing numerical transient simulation and spectral analysis of pressure waves.
引用
收藏
页码:200 / 206
页数:7
相关论文
共 12 条
  • [11] Wood D.J., 1966, American Society of Civil Engineers Proceedings, Journal of the Hydraulics Division, V92, P83, DOI 10.1061/JYCEAJ.0001447
  • [12] NETWORK SYSTEM TRANSIENT CALCULATIONS BY IMPLICIT METHOD
    WYLIE, EB
    STREETER, VL
    STONER, MA
    [J]. SOCIETY OF PETROLEUM ENGINEERS JOURNAL, 1971, 11 (04): : 356 - &