Numerical and experimental investigation of the indoor air quality and thermal comfort performance of a low energy cooling windcatcher with heat pipes and extended surfaces

被引:51
作者
Calautit, John Kaiser [1 ]
Tien, Paige Wenbin [1 ]
Wei, Shuangyu [1 ]
Calautit, Katrina [1 ]
Hughes, Ben [2 ]
机构
[1] Univ Nottingham, Dept Architecture & Built Environm, Nottingham NG7 2TN, England
[2] Univ Strathclyde, Dept Mech & Aerosp Engn, Glasgow G1 1XJ, Lanark, Scotland
关键词
Built environment; Computational modelling; Extended surfaces; Heat pipes; Passive cooling; COMMERCIAL WIND TOWERS; NATURAL VENTILATION; CFD; SIMULATION; CATCHER; TUNNEL; HOT; ENVIRONMENT; BUILDINGS; RECOVERY;
D O I
10.1016/j.renene.2019.06.040
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This work builds on previous experience in windcatcher design, maximising the ventilation rate of the windcatcher, whilst integrating low energy cooling technologies. The present study aims to investigate the thermal comfort and indoor air quality in buildings ventilated with a passive cooling windcatcher integrated with heat pipes and extended surface using numerical modelling, wind tunnel and far-field testing in the UAE during a summer month. Results of the scaled wind tunnel tests showed that the addition of the heat pipes and extended surfaces reduced the airflow through the windcatcher but did not impede the flow even at low outdoor wind speeds, this was further confirmed by the smoke visualisation tests. Analysis of pollutant concentration in the building model showed that the proposed windcatcher configuration was capable of delivering fresh air at a sufficient rate to lower CO2 concentration levels below the recommended guidelines for air quality. The thermal comfort analysis was conducted and it was observed that for the present design, equal distribution of thermal comfort was not achieved due to combination of high air movement, colder temperature and high humidity below the windcatcher which resulted in higher thermal discomfort in this area. Further work is required to develop a suitable control strategy in the form of volume control dampers which would enable the supply flowrate to be monitored and altered as required and optimized the distribution in the occupied space. Field tests data was used to validate the numerical modelling, showing good agreement between both methods. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:744 / 756
页数:13
相关论文
共 38 条
[1]   A proposal to introduce tradable energy savings certificates in the emirate of Abu Dhabi [J].
Afshari, Afshin ;
Friedrich, Luiz .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 55 :1342-1351
[2]   Influence of roof topology on the air distribution and ventilation effectiveness of wind towers [J].
Ameer, Shazia Ahmed ;
Chaudhry, Hassam Nasarullah ;
Agha, Arouge .
ENERGY AND BUILDINGS, 2016, 130 :733-746
[3]  
[Anonymous], 2009, TRANSF MARK EN EFF B
[4]   Experimental investigation of new designs of wind towers [J].
Bahadori, M. N. ;
Mazidi, M. ;
Dehghani, A. R. .
RENEWABLE ENERGY, 2008, 33 (10) :2273-2281
[5]   A STUDY OF SOLAR CHIMNEY ASSISTED WIND TOWER SYSTEM FOR NATURAL VENTILATION IN BUILDINGS [J].
BANSAL, NK ;
MATHUR, R ;
BHANDARI, MS .
BUILDING AND ENVIRONMENT, 1994, 29 (04) :495-500
[6]   CFD simulation of the atmospheric boundary layer: wall function problems [J].
Blocken, Bert ;
Stathopoulos, Ted ;
Carmeliet, Jan .
ATMOSPHERIC ENVIRONMENT, 2007, 41 (02) :238-252
[7]   Performance analysis and improvement of the use of wind tower in hot dry climate [J].
Bouchahm, Yasmina ;
Bourbia, Fatiha ;
Belhamri, Azeddine .
RENEWABLE ENERGY, 2011, 36 (03) :898-906
[8]   Experimentally validated CFD analysis on sampling region determination of average indoor carbon dioxide concentration in occupied space [J].
Bulinska, Anna ;
Popiolek, Zbigniew ;
Bulinski, Zbigniew .
BUILDING AND ENVIRONMENT, 2014, 72 :319-331
[9]   Climatic analysis of a passive cooling technology for the built environment in hot countries [J].
Calautit, John Kaiser ;
Hughes, Ben Richard ;
Nasir, Diana S. N. M. .
APPLIED ENERGY, 2017, 186 :321-335
[10]   Numerical and experimental analysis of a multi-directional wind tower integrated with vertically-arranged heat transfer devices (VHTD) [J].
Calautit, John Kaiser ;
Hughes, Ben Richard ;
O'Connor, Dominic ;
Shahzad, Sally Salome .
APPLIED ENERGY, 2017, 185 :1120-1135