Experimental investigation on heat transfer rate self-adjustment capacity of a novel horizontal double-pipe cooler with eccentric axis structure

被引:0
作者
Zhan, Binfei [1 ,3 ]
Shao, Shuangquan [2 ]
Tian, Changqing [1 ,3 ]
Zhang, Hainan [1 ,3 ]
Zhou, Yuan [3 ]
机构
[1] Chinese Acad Sci, Tech Inst Phys & Chem, Key Lab Technol Space Energy Convers, Beijing 100190, Peoples R China
[2] Huazhong Univ Sci & Technol, Sch Energy & Power Engn, Wuhan 430074, Peoples R China
[3] Univ Chinese Acad Sci, Beijing 100049, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
Horizontal-tube exchanger; Thermosyphon; Double-pipe exchanger; Self-adjustment; COLD CHAIN; ENERGY; SYSTEM; TEMPERATURE; PERFORMANCE; FREQUENCY; VOLUME; THERMOSIPHON; NETWORKS; STRATEGY;
D O I
10.1016/j.ijrefrig.2021.03.023
中图分类号
O414.1 [热力学];
学科分类号
摘要
A novel type of horizontal eccentric tube cooler was proposed that combines the advantages of self adaptive capacity of thermosyphon technology and high heat-transfer efficiency of conventional double pipe exchanger. Compared with the conventional heat-exchange tube evaporator, it has self-adjustment ability of heat transfer rate with rotation angle. Four different structures of horizontal tube cooler with eccentric axis structure were proposed and tested for verifying the self-adjustment capacity performance. Finally, one optimal structure was selected as the recommendation, which has distinct successive self adjustment ability with rotation angle 0-135 degrees, self-adjustment range of heat transfer rate 36.67%, and the lowest heat transfer rate loss 19.66% with about 48% filling rate. It will have revolutionary application significance in some fields requiring heat exchange regulation. (c) 2021 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:43 / 52
页数:10
相关论文
共 44 条
  • [11] Energy evaluation of optimal control strategies for central VWV chiller systems
    Jin, Xinqiao
    Du, Zhimin
    Xiao, Xiaokun
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (5-6) : 934 - 941
  • [12] Energy efficient fuzzy based combined variable refrigerant volume and variable air volume air conditioning system for buildings
    Karunakaran, R.
    Iniyan, S.
    Goic, Ranko
    [J]. APPLIED ENERGY, 2010, 87 (04) : 1158 - 1175
  • [13] Energy Performance Comparison of Inverter based Variable Refrigerant Flow Unitary AC with Constant Volume Unitary AC
    Khatri, Rahul
    Joshi, Anant
    [J]. INTERNATIONAL CONFERENCE ON RECENT ADVANCEMENT IN AIR CONDITIONING AND REFRIGERATION, RAAR 2016, 2017, 109 : 18 - 26
  • [14] Evaluation of energy savings potential of variable refrigerant flow (VRF) from variable air volume (VAV) in the U.S. climate locations
    Kim, Dongsu
    Cox, Sam J.
    Cho, Heejin
    Im, Piljae
    [J]. ENERGY REPORTS, 2017, 3 : 85 - 93
  • [15] Application of artificial neural networks for optimized AHU discharge air temperature set-point and minimized cooling energy in VAV system
    Lee, Jong Man
    Hong, Sung Hyup
    Seo, Byeong Mo
    Lee, Kwang Ho
    [J]. APPLIED THERMAL ENGINEERING, 2019, 153 : 726 - 738
  • [16] Energy saving assessment of a desiccant-enhanced evaporative cooling system in variable air volume applications
    Lee, Sung-Joon
    Kim, Hui-Jeong
    Dong, Hye-Won
    Jeong, Jae-Weon
    [J]. APPLIED THERMAL ENGINEERING, 2017, 117 : 94 - 108
  • [17] Optimization on crucial ejector geometries in a multi-evaporator refrigeration system for tropical region refrigerated trucks
    Li, Shengyu
    Yan, Jia
    Liu, Zhan
    Yao, Yong
    Li, Xianbi
    Wen, Na
    Zou, Guorong
    [J]. ENERGY, 2019, 189
  • [18] Research and development of a permanent-magnet synchronous frequency-convertible centrifugal compressor
    Liu, Hua
    Zhang, Zhiping
    Li, Hongbo
    Wang, Sheng
    Hu, Bin
    Wang, R. Z.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 117 : 33 - 43
  • [19] Maley Matthew J., 2020, APPL ERGON, V85
  • [20] Air conditioning system with enthalpy recovery for space heating and air humidification: An experimental and numerical investigation
    Niemann, Peter
    Schmitz, Gerhard
    [J]. ENERGY, 2020, 213 (213)