Airflow rates by combined natural ventilation with opposing wind-unambiguous solutions for practical use

被引:15
作者
Andersen, Karl Terpager [1 ]
机构
[1] Danish Bldg Res Inst, Dept Energy & Environm, DK-2970 Horsholm, Denmark
关键词
combined natural ventilation; natural ventilation; wind; thermal buoyancy; multiple solutions; stability;
D O I
10.1016/j.buildenv.2005.09.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Analysis of possible airflow rates by combined natural ventilation with opposing wind in rooms with two openings shows multiple solutions, instability and hysteresis. In this paper, it is analysed to what extent these phenomena should be considered under practical conditions. The analysis shows that unambiguous solutions can be obtained if difference between indoor and outdoor temperature is known at start, i.e. when heat sources are switched on and ventilation openings are opened. Discontinuities in airflow rates occur under certain specific conditions. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:534 / 542
页数:9
相关论文
共 4 条
[1]  
ANDERSEN P, 2000, P 21 AIVC C NETH SEP, P1
[2]   Chromate passivation of hot dipped Zn25Al alloy coatings [J].
Li, Y ;
Wang, H ;
Hou, B ;
Feng, F ;
Wei, X .
BRITISH CORROSION JOURNAL, 2001, 36 (01) :56-58
[3]   Some examples of solution multiplicity in natural ventilation [J].
Li, YG ;
Delsante, A ;
Chen, ZD ;
Sandberg, M ;
Andersen, A ;
Bjerre, M ;
Heiselberg, P .
BUILDING AND ENVIRONMENT, 2001, 36 (07) :851-858
[4]  
SELBY MS, 1967, STANDARD MATH TABLES