A new method using ultrasonic for partial discharge pattern recognition

被引:0
作者
Li, YQ [1 ]
Lu, FC [1 ]
Xin, BO [1 ]
Chen, ZY [1 ]
机构
[1] N China Elect Power Univ, Dept Elect Engn, BaoDing 071003, HeBei, Peoples R China
来源
POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS | 2002年
关键词
artificial neural networks; fractal; partial discharge; pattern recognition; ultrasonic;
D O I
暂无
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
The Partial discharge measurements on power transformer are studied with a new method toward discrimination and classification of different discharge models. Based on characteristics of partial discharge ultrasonic signal are non-linear and non-stationary, fractal theory is adopted to extract fractal parameters from ultrasonic signal of transformer partial discharge in this paper. The self-similarity character of ultrasonic signal for partial discharge is analyzed. The fractal theory and its parameters calculation are introduced. Experiments are done about several typical transformer partial discharge models. The fractal parameters (box counting dimension and lacunarity) are calculated in different model's ultrasonic signals, The calculate result shows that fractal parameters are dissimilarity of box counting dimension and lacunarity in different transformer partial discharge ultrasonic signals. The artificial neural networks is used to recognize discharge patterns. The result shows the fractal method is effective for transformer partial discharge pattern recognition.
引用
收藏
页码:1004 / 1007
页数:4
相关论文
共 9 条