Application of interleaved circuitry to improve evaporator effectiveness and COP of a packaged AC system

被引:20
作者
Bahman, Ammar M. [1 ]
Groll, Eckhard A. [1 ]
机构
[1] Purdue Univ, Sch Mech Engn, Ray W Herrick Labs, 177 S Russell St, W Lafayette, IN 47907 USA
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2017年 / 79卷
关键词
Packaged air conditioning; Air maldistribution; Interleaved circuitry; Cooling capacity; COP; Model; AIR-FLOW MALDISTRIBUTION; HEAT-PUMP; TUBE EVAPORATORS; PERFORMANCE; FIN; REFRIGERANT; COMPENSATION; OPTIMIZATION;
D O I
10.1016/j.ijrefrig.2017.03.026
中图分类号
O414.1 [热力学];
学科分类号
摘要
Highly constrained air flow pathways as experienced in tightly packaged air conditioning systems result in air flow maldistribution problems in the evaporators. The interleaved circuitry method, where the refrigerant from a circuit with high air flow is routed to a circuit with low air flow and vice-versa, has been investigated to passively reduce the air maldistribution effect. Air velocity measurements have been conducted in psychrometric chambers and the measurement locations have been defined by the log-Tchebycheff rule. The velocity profile was obtained by Lagrange Interpolation method as percentage values. The performance of the interleaved circuitry method was compared to the baseline circuitry at different operating conditions. The results show that the interleaved circuitry method uniforms the superheat of the individual circuits and improves the cooling capacity and COP by up to 16.6% and 12.4%, respectively. Furthermore, the tuned model predicted the evaporator cooling capacity within a mean absolute error of approximately 10%. (C) 2017 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:114 / 129
页数:16
相关论文
共 51 条
  • [1] Airflow maldistribution and the performance of a packaged air conditioning unit evaporator
    Aganda, AA
    Coney, JER
    Sheppard, CGW
    [J]. APPLIED THERMAL ENGINEERING, 2000, 20 (06) : 515 - 528
  • [2] [Anonymous], 1980, USER GUIDE MINPACK 1
  • [3] [Anonymous], 2006, THESIS
  • [4] [Anonymous], 1998, Technical Report DFVLR-FB 88-28
  • [5] Bach C. K, 2014, THESIS
  • [6] Mitigation of air flow maldistribution in evaporators
    Bach, Christian K.
    Groll, Eckhard A.
    Braun, James E.
    Horton, W. Travis
    [J]. APPLIED THERMAL ENGINEERING, 2014, 73 (01) : 879 - 887
  • [7] Bahman A. M., 2016, INT REFR AIR COND C
  • [8] Bell I.H., 2015, Air conditioning and heat pump model (achp) source code version 1.5
  • [9] Bergman T.L., 2011, Introduction to Heat Transfer, DOI DOI 10.1016/J.APPLTHERMALENG.2011.03.022
  • [10] Experimental investigation of the effects of airflow nonuniformity on performance of a fin-and-tube heat exchanger
    Blecich, Paolo
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 59 : 65 - 74