Experimental and theoretical analysis of liquid desiccant dehumidification process based on an advanced hybrid air-conditioning system

被引:70
作者
Chen, Yao [1 ]
Zhang, Xiaosong [1 ]
Yin, Yonggao [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
关键词
Experimental study; Liquid desiccant; Heat and mass transfer coefficients; Dehumidification; Heat pump; MASS-TRANSFER COEFFICIENTS; FALLING-FILM ABSORPTION; PERFORMANCE ANALYSIS; TRANSFER MODEL; PACKED-COLUMN; HEAT; DEHUMIDIFIER/REGENERATOR;
D O I
10.1016/j.applthermaleng.2015.12.066
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the characteristic study of the air dehumidification process using liquid desiccant with low-temperature and low-concentration. Experiment research was conducted with an advanced liquid desiccant system driven by heat pump, and experimental data was acquired with the variation of the parameters of the inlet air and desiccant solution. During the experiment, LiCl solution was used as the liquid desiccant, while the temperature of the desiccant solution was lower than 20 degrees C and the mass concentration of the desiccant solution was kept below 0.33. In order to describe this special air dehumidification process, the classical NTU-Le model was modified upon the parameter ranges of the air and desiccant solution in this study. Furthermore, a new method for determining the coupled heat and mass transfer coefficients between air and desiccant solution was developed. With this method, heat and mass transfer correlations were derived from the experimental data to predict the performance of this special air dehumidification_ process. Based on these studies, an additional experiment was carried out to validate the accuracy of the corrected NTU-Le model, as well as the new evaluation method and the new heat and mass transfer correlations. Finally, the effects of the inlet thermophysical properties of air and desiccant solution on the performance of the dehumidifier were investigated. In addition, the real-time performance of the new hybrid system under a typical summer condition was analyzed. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:387 / 399
页数:13
相关论文
共 34 条
[1]   Performance analysis of a membrane liquid desiccant air-conditioning system [J].
Abdel-Salam, Ahmed H. ;
Ge, Gaoming ;
Simonson, Carey J. .
ENERGY AND BUILDINGS, 2013, 62 :559-569
[2]   Predictions of moisture removal rate and dehumidification effectiveness for structured liquid desiccant air dehumidifier [J].
Abdul-Wahab, SA ;
Zurigat, YH ;
Abu-Arabi, MK .
ENERGY, 2004, 29 (01) :19-34
[3]   Evaluation of heat and mass transfer coefficients in a gauze-type structured packing air dehumidifier operating with liquid desiccant [J].
Al-Farayedhi, AA ;
Gandhidasan, P ;
Al-Mutairi, MA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (03) :330-339
[4]  
[Anonymous], 201092006 GBT
[5]   A simple analytical method to estimate all exit parameters of a cross-flow air dehumidifier using liquid desiccant [J].
Bassuoni, M. M. .
JOURNAL OF ADVANCED RESEARCH, 2014, 5 (02) :175-182
[6]   Performance analysis of a hybrid air-conditioning system dehumidified by liquid desiccant with low temperature and low concentration [J].
Chen, Yao ;
Yin, Yonggao ;
Zhang, Xiaosong .
ENERGY AND BUILDINGS, 2014, 77 :91-102
[7]   Comparison between random and structured packings for dehumidification of air by lithium chloride solutions in a packed column and their heat and mass transfer correlations [J].
Chung, TW ;
Ghosh, TK ;
Hines, AL .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (01) :192-198
[8]   The role of the thermally activated desiccant cooling technologies in the issue of energy and environment [J].
Enteria, Napoleon ;
Mizutani, Kunio .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (04) :2095-2122
[9]   Heat and mass transfer coefficients of falling-film absorption process [J].
Fujita, I ;
Hihara, E .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2005, 48 (13) :2779-2786
[10]   Combination of ground source heat pumps with chemical dehumidification of air [J].
Gasparella, A ;
Longo, GA ;
Marra, R .
APPLIED THERMAL ENGINEERING, 2005, 25 (2-3) :295-308