Identification of armature, field, and saturated parameters of a large steam turbine-generator from operating data

被引:19
作者
Karayaka, HB [1 ]
Keyhani, A
Agrawal, BL
Selin, DA
Heydt, GT
机构
[1] Ohio State Univ, Dept Elect Engn, Columbus, OH 43210 USA
[2] Arizona Publ Serv Co, Phoenix, AZ USA
[3] Arizona State Univ, Tempe, AZ USA
基金
美国国家科学基金会;
关键词
parameter identification; large utility generators; saturation modeling; artificial neural networks; field winding degradation; state estimation;
D O I
10.1109/60.866997
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a step by step identification procedure of armature, field and saturated parameters of a large steam turbine-generator from real time operating data. First, data from a small excitation disturbance is utilized to estimate armature circuit parameters of the machine. Subsequently, for each set of steady state operating data, saturable mutual inductances L-ads and L-aqs are estimated. The recursive maximum likelihood estimation technique is employed for identification in these first two stages. An artificial neural network (ANN) based estimator is later used to model these saturated inductances based on the generator operating conditions. Finally, using the estimates of the armature circuit parameters, the field winding and some damper winding parameters are estimated using an Output Error Method (OEM) of estimation. The developed models are validated with measurements not used in the training of ANN and with large disturbance responses.
引用
收藏
页码:181 / 187
页数:7
相关论文
共 22 条
[1]   A GENERAL EQUIVALENT-CIRCUIT (GEC) OF ELECTRIC MACHINES INCLUDING CROSS-COUPLING SATURATION AND FREQUENCY-EFFECTS [J].
BOLDEA, I ;
NASAR, SA .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1988, 3 (03) :689-695
[2]   CAUSES OF DISCREPANCIES ON CALCULATION OF ROTOR QUANTITIES AND EXACT EQUIVALENT DIAGRAMS OF SYNCHRONOUS MACHINE [J].
CANAY, IM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (07) :1114-&
[3]   An artificial-neural-network method for the identification of saturated turbogenerator parameters based on a coupled finite-element state-space computational algorithm [J].
Chaudhry, SR ;
AhmedZaid, S .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1995, 10 (04) :625-633
[4]  
DEMCKO JA, 1989, GS6475 EPRI, V2
[5]   REPRESENTATION OF SATURATION IN SYNCHRONOUS MACHINES [J].
DEMELLO, FP ;
HANNETT, LN .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1986, 1 (04) :8-18
[6]   DETERMINATION OF THE PARAMETERS REPRESENTING THE CROSS-MAGNETIZING EFFECT IN SATURATED SYNCHRONOUS MACHINES [J].
ELSERAFI, AM ;
WU, J ;
DANDENO, PL .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1993, 8 (03) :333-342
[7]   EXPERIMENTAL-STUDY OF THE SATURATION AND THE CROSS-MAGNETIZING PHENOMENON IN SATURATED SYNCHRONOUS MACHINES [J].
ELSERAFI, AM ;
ABDALLAH, AS ;
ELSHERBINY, MK ;
BADAWY, EH .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1988, 3 (04) :815-823
[8]   IDENTIFICATION OF GENERALIZED MODELS OF SYNCHRONOUS MACHINES FROM TIME-DOMAIN TESTS [J].
KAMWA, I ;
VIAROUGE, P ;
DICKINSON, EJ .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1991, 138 (06) :485-498
[9]  
KIRTLEY JL, 1994, IEEE T PWRS, V9, P269
[10]   SMALL PERTURBATION LINEARIZATION OF SATURATED SYNCHRONOUS MACHINE EQUATIONS [J].
LEMAY, J ;
BARTON, TH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (01) :233-+