Analysis of the Working Characteristics of the Natural Draft Cooling Tower on the Laboratory Model

被引:0
作者
Badriev, Ayrat, I [1 ]
Sharifullin, Vilen N. [2 ]
Sharifullin, Andrew, V [3 ]
机构
[1] Kazan Fed Univ, Kazan, Tatarstan, Russia
[2] Kazan State Power Engn Univ, Kazan, Tatarstan, Russia
[3] Kazan Natl Res Technol Univ, Kazan, Tatarstan, Russia
来源
HELIX | 2019年 / 9卷 / 05期
关键词
Cooling Tower; Irregularity of Irrigation; Performance; Laboratory Installation; Cooling Efficiency; PERFORMANCE;
D O I
10.29042/2019-5539-5544
中图分类号
Q81 [生物工程学(生物技术)]; Q93 [微生物学];
学科分类号
071005 ; 0836 ; 090102 ; 100705 ;
摘要
The summer season becomes difficult for chimney-type cooling tower. Due to the hot atmospheric air entering the apparatus, insufficient heat removal occurs, which means undercooling of water. Ultimately, this leads to a decrease in the power of the steam turbine of a thermal power plant. In the summer, an experimental study of the irregularity of the irrigation of the cooled water by the natural cooling tower was carried out. A significant irregularity in the density of irrigation over the cross section of the apparatus was established. The regression dependences of the temperature difference and cooling power are constructed taking into account the irregularity of the irrigation density. The obtained performance characteristics are tested on a laboratory model of the cooling tower. It is established that the nature of the regression models of temperature difference and cooling power from the density of irrigation of the natural cooling tower and its models are of the same nature. Thus, in a laboratory setup, confirmation of the performance of a full-scale cooling tower was obtained. Comparing the nature of the dependences of the laboratory model and the dependences of the cooling tower, it should be noted that the dependences of the temperature difference are expressed parabolic, and the cooling capacity on the density of irrigation cubic equation. The performance characteristics of a full-scale cooling tower allow us to judge its effectiveness by its sections, functioning in conditions of irregular irrigation.
引用
收藏
页码:5539 / 5544
页数:6
相关论文
共 9 条
[1]   Cooling towers performance in a changing climate: Techno-economic modeling and design optimization [J].
Ayoub, Ali ;
Gjorgiev, Blaze ;
Sansavini, Giovanni .
ENERGY, 2018, 160 :1133-1143
[2]  
Berman L.D., 1949, EVAPORATIVE COOLING
[3]  
Davletshin F.M., 2006, CHEM CHEM TECHNOLOGY, V49, P90
[4]  
Gmurman V. E., 1992, PROBABILITY THEORY M
[5]  
Kalatuzov V.A., 2006, ENERGY CONSERVATION
[6]  
Li Xiaoxiao, 2017, INT J HEAT MASS TRAN
[7]   Experimental investigation on the performance of wet cooling towers with defects in power plants [J].
Ning, Tao ;
Chong, Daotong ;
Jia, Mingxiao ;
Wang, Jinshi ;
Yan, Junjie .
APPLIED THERMAL ENGINEERING, 2015, 78 :228-235
[8]   Investigation on the influence of injection direction on the spray cooling performance in natural draft dry cooling tower [J].
Sun, Yubiao ;
Guan, Zhiqiang ;
Gurgenci, Hal ;
Hooman, Kamel ;
Li, Xiaoxiao ;
Xia, Lin .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 110 :113-131
[9]   Numerical simulation of flow in a natural draft wet cooling tower The effect of radial thermofluid fields [J].
Williamson, N. ;
Armfield, S. ;
Behnia, M. .
APPLIED THERMAL ENGINEERING, 2008, 28 (2-3) :178-189