Real-Time Electromagnetic Transient Simulation of Multi-Terminal HVDC-AC Grids Based on GPU

被引:15
作者
Sun, Jingfan [1 ]
Debnath, Suman [2 ]
Saeedifard, Maryam [1 ]
Marthi, Phani R., V [2 ,3 ]
机构
[1] Georgia Inst Technol, Sch Elect & Comp Engn, Atlanta, GA 30332 USA
[2] Oak Ridge Natl Lab, Knoxville, TN 37932 USA
[3] Missouri Univ Sci & Technol, Rolla, MO 65409 USA
关键词
Graphics processing unit; multiterminal HVdc systems; real-time simulation; MODULAR MULTILEVEL CONVERTER; POWER-SYSTEMS; MMC; MODELS;
D O I
10.1109/TIE.2020.3005059
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
High-fidelity electromagnetic transient (EMT) simulation plays a critical role in understanding the dynamic behavior and fast transients involved in operation, control, and protection of multiterminal dc (MTdc) grids. This article proposes a cost-effective high-performance real-time EMT simulation platform for large-scale cross-continental MTdc grids based on graphics processing unit (GPU). Fast dynamic transients from both ac and dc networks are captured in real time with 5 mu s time step, using advanced hybrid-discretized modular multilevel converter model, frequency-dependent transmission line model, and EMT-type model of synchronous generators. The proposed simulation platform i) assembles detailed EMT models of all components within an MTdc-ac grid into a single platform. This setup provides a complete simulation solution to capture fast transient signals required for high-bandwidth controller design and protection studies without any compromise; ii) implements the first GPU-based simulation architecture and corresponding algorithms for MTdc-ac grids with real-time performance at scales of 1s; iii) is highly efficient and balances the high utilization of GPU resources and low latency required for the simulation; and iv) outperforms the existing central processing unit- or digital signal processor (DSP)/field-programmable gate array-based simulators in terms of its higher scalability on large-scale MTdc-ac grids and superior price-performance ratio on the hardware. Accuracy and performance of the proposed platform are evaluated with respect to the reference results from power system computer aided design (PSCAD)/EMTdc environment.
引用
收藏
页码:7002 / 7011
页数:10
相关论文
共 39 条
[1]  
[Anonymous], 2013, 533 CIGRE
[2]  
[Anonymous], 2013, 563 CIGRE
[3]  
[Anonymous], 1998, POWER SYSTEM DYNAMIC
[4]   Enhanced Model and Real-Time Simulation Architecture for Modular Multilevel Converter [J].
Ashourloo, Mojtaba ;
Mirzahosseini, Ramin ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (01) :466-476
[5]  
Chaudhuri NR, 2014, MULTI-TERMINAL DIRECT-CURRENT GRIDS: MODELING, ANALYSIS, AND CONTROL, P1, DOI 10.1002/9781118960486
[6]  
CIGRE WG B4-57, 2014, Tech. Rep. CIGRE Tech. Brochure 604
[7]  
Debnath S., 2019, Models and methods for assessing the value of HVDC and MVDC technologies in modern power grids
[8]  
Debnath S, 2016, IEEE ENER CONV
[9]  
Debnath S, 2018, IEEE IND ELEC, P6007, DOI 10.1109/IECON.2018.8591085
[10]  
Debnath S, 2018, IEEE ENER CONV, P5196, DOI 10.1109/ECCE.2018.8558031