Transient Electric Field Analysis for Polluted Composite Insulators Under HVDC Stress

被引:5
|
作者
Nandi, Sounak [1 ]
Reddy, Subba B. [1 ]
机构
[1] Indian Inst Sci, Dept Elect Engn, High Voltage Lab, Bangalore 560012, Karnataka, India
关键词
Insulators; Conductivity; Pollution; Boundary conditions; Surface contamination; HVDC transmission; Transient analysis; HVDC; Composite insulator; pollution; electric potential;
D O I
10.1109/TPWRD.2020.2987143
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The present investigation highlights simulation study performed considering the temporal transformation of the electric field from capacitive to resistive. The effect of uniform pollution, single dry-band, multiple dry-bands and non-uniform pollution are studied in detail. The simulation results indicate the effect of surface current can literally decrease the voltage withstand capability of the insulator. The simulations are carried out under time domain so that the simplicity and the physical integrity of the problem is retained. Experimental investigations are conducted to verify the obtained theoretical results. Investigations show that there is substantial decrement of scintillation inception voltage with time, further experimental observations are explained based on the theoretical results that have been derived. Based on the theoretical and experimental observations, it is thought that proper insulation design and optimal creepage should be provided under DC, as field distribution can change over a period with increasing surface conductivity.
引用
收藏
页码:607 / 617
页数:11
相关论文
共 50 条
  • [1] Charge Simulation Based Electric Field Analysis of Composite Insulators for HVDC Lines
    He, Jiahong
    Gorur, Ravi S.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (06) : 2541 - 2548
  • [2] Behavior of composite insulators under HVDC stress, from creeping discharges until flashover
    Aliouat, Sihem
    Nacer, Azzeddine
    Boudjit, Kamel
    Chiheb, Sofiane
    Moulai, Hocine
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 241
  • [3] Electric Field Modelling of Composite High Voltage Insulators
    Reddy, Subba B.
    Kumar, Anuja
    Shashikala, A.
    Ravishankar, K., V
    2009 ANNUAL IEEE INDIA CONFERENCE (INDICON 2009), 2009, : 484 - +
  • [4] Transient Surface Electric Field Measurement of the Composite Insulators Using an Integrated Optics Sensor
    Zhang, Jiahong
    Li, Weichang
    Zhang, Jing
    Li, Yingna
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2024, 73
  • [5] Analysis of electric field and leakage current of glass and porcelain insulators under clean and polluted conditions: A comparative study of three profiles
    Khan, Sana
    Alam, Shahid
    Saleem, Muhammad Zaheer
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 239
  • [6] Study on the Behavior of Polluted Insulators under Lightning Impulse Stress
    Taheri, Sh
    Gholami, A.
    Mirzaei, M.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2009, 37 (12) : 1321 - 1333
  • [7] Study on the Behavior of Polluted Insulators Under Lightning Impulse Stress
    Taheri, Sh
    Gholami, A.
    Mirzaie, M.
    2008 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2008, : 341 - +
  • [8] Simulation of Electrostatic Field Across HVDC Composite Insulators
    Nandi, Sounak
    Reddy, B. Subba
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 2, 2020, 599 : 1453 - 1466
  • [9] Electric Field Analysis of Spacer Cable Systems under Polluted Conditions
    Espino-Cortes, Fermin P.
    Ramirez-Vazquez, Isaias
    Gomez, Pablo
    2014 ELECTRICAL INSULATION CONFERENCE (EIC), 2014, : 231 - 234
  • [10] Electric Field Analysis of composite insulators under dry condition using charge simulation method
    Kiruthika, M.
    Maheswari, R. V.
    2016 INTERNATIONAL CONFERENCE ON ENERGY EFFICIENT TECHNOLOGIES FOR SUSTAINABILITY (ICEETS), 2016, : 609 - 612