Synchrophasor measurement-based fault location technique for multi-terminal multi-section non-homogeneous transmission lines

被引:20
作者
Wu, Ting [1 ]
Chung, Chi-Yung [2 ]
Kamwa, Innocent [3 ]
Li, Jiayong [1 ]
Qin, Mingwen [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Elect Engn, Hong Kong, Hong Kong, Peoples R China
[2] Univ Saskatchewan, Dept Elect & Comp Engn, Saskatoon, SK, Canada
[3] Hydro Quebec IREQ, Power Syst & Math, Varennes, PQ, Canada
关键词
DETECTION/LOCATION TECHNIQUE; ALGORITHM; DISCRIMINATION;
D O I
10.1049/iet-gtd.2015.0927
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study presents a fault-location technique for multi-terminal multi-section non-homogeneous transmission lines which combine overhead lines with underground power cables, by using voltage and current synchrophasors obtained from phasor measurement units. First, a faulty line branch is selected to narrow down the suspected faulty area. Then, the faulty section and the exact fault location can be identified by calculating the normalised fault distance for each section on the selected faulty branch. Computational burden of the proposed analytical scheme is very low because it avoids iterative computations. Promising simulation results show that the proposed fault location technique can accurately locate the fault regardless of the fault type, fault resistance, fault location, pre-fault loading and line parameters inaccuracies.
引用
收藏
页码:1815 / 1824
页数:10
相关论文
共 18 条
  • [11] A new PMU-based fault detection/location technique for transmission lines with consideration of arcing fault discrimination - Part II: Performance evaluation
    Lin, YH
    Liu, CW
    Chen, CS
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) : 1594 - 1601
  • [12] A universal fault location technique for N-terminal (N ≥ 3) transmission lines
    Liu, Chih-Wen
    Lien, Kai-Ping
    Chen, Ching-Shan
    Jiang, Joe-Air
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) : 1366 - 1373
  • [13] A Fault Location Technique for Two-Terminal Multisection Compound Transmission Lines Using Synchronized Phasor Measurements
    Liu, Chih-Wen
    Lin, Tzu-Chiao
    Yu, Chi-Shan
    Yang, Jun-Zhe
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (01) : 113 - 121
  • [14] A Fault Classification and Localization Method for Three-Terminal Circuits Using Machine Learning
    Livani, Hanif
    Evrenosoglu, Cansin Yaman
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) : 2282 - 2290
  • [15] Synchronized phasor measurements in power systems
    Phadke, A.G.
    [J]. IEEE Computer Applications in Power, 1993, 6 (02): : 10 - 15
  • [16] Robust fault location of transmission lines by synchronised and unsynchronised wide-area current measurements
    Salehi-Dobakhshari, Ahmad
    Ranjbar, Ali Mohammad
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (09) : 1561 - 1571
  • [17] Phasor measurement unit placement framework for enhanced wide-area situational awareness
    Sodhi, Ranjana
    Sharieff, Md Imran
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (02) : 172 - 182
  • [18] Fault Location for Underground Power Cable Using Distributed Parameter Approach
    Yang, Xia
    Choi, Myeon-Song
    Lee, Seung-Jae
    Ten, Chee-Wooi
    Lim, Seong-Il
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (04) : 1809 - 1816