Fault Interpretation Algorithm Using Frequency-Response Analysis of Power Transformers

被引:42
作者
Gonzales, J. C. [1 ,2 ]
Mombello, E. E. [1 ,2 ,3 ]
机构
[1] Univ Nacl San Juan, CONICET, J5400ARL, San Juan, Argentina
[2] Univ Nacl San Juan, Inst Energia Elect, J5400ARL, San Juan, Argentina
[3] Univ Nacl San Juan, Inst Energia Elect, UE IEE UNSJ CONICET, J5400ARL, San Juan, Argentina
关键词
Discrete wavelet transform; expert knowledge; frequency regions; power transformers; sweep frequency-response analysis (SFRA); vector fitting;
D O I
10.1109/TPWRD.2015.2448524
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Sweep frequency-response analysis (SFRA) is a powerful technique to detect mechanical damage in transformer windings, such as deformations and displacements, as well as other failures, helping to prevent severe damage. Since SFRA is a sensitive diagnostic technique, there are these days several commercially available measurement instruments to perform the tests, but the failure interpretation is usually based on expert opinion. One of the most advisable ways to face the task of interpretation of SFRA test results is the use of mathematical indices to detect abnormalities along with an interpretation scheme. The failure interpretation methodology of SFRA tests must establish the possible relationships between frequency ranges and specific failures, because different failure types can be detected in different frequency ranges of the SFRA trace. This paper proposes a new methodology for power transformer failure diagnosis using the relationships between the different decomposition levels of the original trace obtained with the use of the discrete wavelet transform and the definition of frequency regions with variable limits, according to the shape of the trace. Moreover, an interpretation map and a vector fitting analysis are also proposed in order to establish a specific failure.
引用
收藏
页码:1034 / 1042
页数:9
相关论文
共 13 条
[1]  
[Anonymous], 2013, C571492012 IEEE
[2]  
[Anonymous], 2005, ELECT POWER IND PEOP
[3]  
[Anonymous], 2008, CIGRE PUBL
[4]  
BJERKAN E, 2005, 6 INT C POW SYST TRA
[5]   Detection of Failures Within Transformers by FRA Using Multiresolution Decomposition [J].
Gonzales Arispe, Jimmy Cesar ;
Esteban Mombello, Enrique .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (03) :1127-1137
[6]  
Gonzales J. C., 2012, IEEE 6 POW EN SOC TR
[7]   Rational approximation of frequency domain responses by vector fitting [J].
Gustavsen, B ;
Semlyen, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) :1052-1061
[8]  
Heindl M., 2009, Paper D-26
[9]  
IEC, 2012, 6007618 IEC
[10]   Modeling Power Transformers to Support the Interpretation of Frequency-Response Analysis [J].
Mitchell, Steven D. ;
Welsh, James S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2705-2717