To study the effect of different parameters on the thermal performance of ground-air heat exchanger system: In situ measurement

被引:27
作者
Agrawal, Kamal Kumar [1 ]
Misra, Rohit [2 ]
Agrawal, Ghanshyam Das [1 ]
机构
[1] Malaviya Natl Inst Technol, Mech Engn Dept, Jaipur, Rajasthan, India
[2] Govt Engn Coll, Mech Engn Dept, Ajmer, India
关键词
Ground air heat exchanger; Sub-soil water trickling system; Soil moisture content; Pipe length; Cooling capacity; Effectiveness; TRANSIENT SEMIANALYTICAL MODEL; EARTH; ENERGY; DESIGN; VALIDATION; HOT;
D O I
10.1016/j.renene.2019.08.065
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the present experimental work, two identical real field experimental setups (with dry soil and wet soil) of ground-air heat exchanger (GAHE) have been developed in order to evaluate the influence of change in inlet air temperature, airflow velocity, diameter of pipe and soil moisture content on the thermal performance of GAHE system. Influence of these parameters on the required pipe length to produce a specified drop in air temperature has also been investigated. Results reveal that the drop in air temperature achieved from GAHE having dry soil is 11.2 degrees C at 60 m pipe length, whereas, for GAHE with wet soil having 20% moisture, the same amount of drop in air temperature is obtained at a pipe length of 28 m only. Moreover, upon increasing the airflow velocity from 2 m/s to 10 m/s, cooling capacity of GAHE with dry soil, wet soil with 5% moisture and wet soil with 20% moisture increases by 122%, 185% and 220%, respectively, after 6 h of operation, but the effectiveness of the GAHE system with dry soil, wet soil with 5% moisture and wet soil with 20% moisture decreases by 55.4%, 42.5% and 36.2%, respectively. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2070 / 2083
页数:14
相关论文
共 41 条
[1]   Effect of different design aspects of pipe for earth air tunnel heat exchanger system: A state of art [J].
Agrawal, Kamal Kumar ;
Misra, Rohit ;
Das Agrawal, Ghanshyam ;
Bhardwaj, Mayank ;
Jamuwa, Doraj Kamal .
INTERNATIONAL JOURNAL OF GREEN ENERGY, 2019, 16 (08) :598-614
[2]   Effect of soil moisture contents on thermal performance of earth-air-pipe heat exchanger for winter heating in arid climate: In situ measurement [J].
Agrawal, Kamal Kumar ;
Yadav, Tejpal ;
Misra, Rohit ;
Das Agrawal, Ghanshyam .
GEOTHERMICS, 2019, 77 :12-23
[3]   A review on effect of geometrical, flow and soil properties on the performance of Earth air tunnel heat exchanger [J].
Agrawal, Kamal Kumar ;
Das Agrawal, Ghanshyam ;
Misra, Rohit ;
Bhardwaj, Mayank ;
Jamuwa, Doraj Kamal .
ENERGY AND BUILDINGS, 2018, 176 :120-138
[4]   Experimental study to investigate the effect of water impregnation on thermal performance of earth air tunnel heat exchanger for summer cooling in hot and arid climate [J].
Agrawal, Kamal Kumar ;
Misra, Rohit ;
Yadav, Tejpal ;
Das Agrawal, Ghanshyam ;
Jamuwa, Doraj Kamal .
RENEWABLE ENERGY, 2018, 120 :255-265
[5]   Parametric study on thermal performance of horizontal earth pipe cooling system in summer [J].
Ahmed, S. F. ;
Amanullah, M. T. O. ;
Khan, M. M. K. ;
Rasul, M. G. ;
Hassan, N. M. S. .
ENERGY CONVERSION AND MANAGEMENT, 2016, 114 :324-337
[6]  
[Anonymous], 1994, EXPT METHODS ENG
[7]   Optimization methods applied to renewable and sustainable energy: A review [J].
Banos, R. ;
Manzano-Agugliaro, F. ;
Montoya, F. G. ;
Gil, C. ;
Alcayde, A. ;
Gomez, J. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (04) :1753-1766
[8]   Parametric study on thermal performance of earth-to-air heat exchanger used for cooling of buildings [J].
Benhammou, Mohammed ;
Draoui, Belkacem .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 44 :348-355
[9]  
Birol F., 2018, The future of cooling: Opportunities for energy-efficient air conditioning
[10]   Design evaluation of Earth-Air Heat Exchangers with multiple ducts [J].
Brum, Ruth S. ;
Ramalho, Jairo V. A. ;
Rodrigues, Michel K. ;
Rocha, Luiz A. O. ;
Isoldi, Liercio A. ;
Dos Santos, Elizaldo D. .
RENEWABLE ENERGY, 2019, 135 :1371-1385