Building energy; Thermal comfort; Building overcooling; Cold thermal discomfort; Warm and hot climates; ADAPTIVE THERMAL COMFORT; NATURALLY VENTILATED BUILDINGS; MODEL-PREDICTIVE CONTROL; PERFORMANCE SIMULATION; RESIDENTIAL BUILDINGS; OFFICE BUILDINGS; SUMMER FINDINGS; HUMID CLIMATES; TEMPERATURE; HOT;
D O I
10.1016/j.enbuild.2022.111938
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Around 18% of global carbon emissions can be attributed to building heating or cooling, driven by the adoption of "international" thermal comfort standards such as ASHRAE-55, which imply an homogenous indoor environment. We argue that the importation of such standards to warm climates results in indoor cold discomfort due to "overcooling": a phenomenon anecdotally recognised worldwide but not studied or defined systematically. Unlike under-or over-heating, overcooling is the purposeful over-expenditure of energy, that creates conditions of cold thermal discomfort. We examine data for warm and temperate climates from a global thermal comfort database spanning 27 countries with over 90,000 occupant responses to investigate overcooling of air-conditioned buildings. We suggest that overcooling is best defined by taking the intersection of thermal sensation and preference and, using this definition, we find that 17% of building occupants in the examined data can be classed as being overcooled. We estimate the cooling energy demand of overcooling imposed through the adoption of the ASHRAE-55 standard using computer simulations that move building occupants from being overcooled to comfortable. The results suggest around 15% of cooling energy demand could be saved through a simple upward adjustment of set-point temperatures by 2 degrees C in warm climates. Such an adjustment in the Global South, which contains the majority of the warm regions of the Earth, could have a dramatic impact on the evolution of future cooling energy demand which is expected to triple by 2050.(c) 2022 Elsevier B.V. All rights reserved.
引用
收藏
页数:13
相关论文
共 116 条
[1]   Thermal comfort evaluation in campus classrooms during room temperature adjustment corresponding to demand response [J].
Aghniaey, Sama ;
Lawrence, Thomas M. ;
Sharpton, Tara Nicole ;
Douglass, Samuel Paul ;
Oliver, Tucker ;
Sutter, Morgan .
BUILDING AND ENVIRONMENT, 2019, 148 :488-497
[2]   Energy consumption in buildings: A correlation for the influence of window to wall ratio and window orientation in Tripoli, Libya [J].
Alghoul, Samah K. ;
Rijabo, Hassan G. ;
Mashena, Mohamed E. .
JOURNAL OF BUILDING ENGINEERING, 2017, 11 :82-86
[3]   The Energy Cost of Cold Thermal Discomfort in the Global South [J].
Alnuaimi, Abdulla N. ;
Natarajan, Sukumar .
BUILDINGS, 2020, 10 (05)
[5]  
[Anonymous], 2007, 152512007 INDOOR ENV
[6]  
[Anonymous], 2021, NOAA
[7]  
[Anonymous], 2004, 9012004 ASHRAE AS
[8]  
[Anonymous], 2005, ERGONOMICS THERMAL E, DOI DOI 10.1016/J.SOILDYN.2004.11.005
[9]  
[Anonymous], 2020, Energy Technology Perspectives 2020: Special Report on Clean Energy Innovation, DOI 10.1787/ab43a9a5-en
[10]  
[Anonymous], 2010, THERMAL ENV CONDITIO