Tolerant control for multiple faults of sensors in VAV systems

被引:24
作者
Du, Zhimin [1 ]
Jin, Xinqiao [1 ]
机构
[1] Shanghai Jiao Tong Univ, Sch Mech Engn, Shanghai 200030, Peoples R China
关键词
tolerant control; multiple faults; sensor; variable air volume; detection; isolation; reconstruction;
D O I
10.1016/j.enconman.2006.09.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
Principal component analysis, joint angle plots and reconstruction schemes are presented in this paper to detect, isolate and evaluate multiple sensors faults occurring in variable air volume (VAV) systems. Multi-level principal component analysis models, including system level and local level, are built to detect multiple faults occurring in VAV systems. As the initial detection, a system level model is used to discover the abnormalities in view of the whole systems. Two local level models are used to further confirm the occurrence of the faults. Moreover, with the multiple faults separated into different locations by the two local level detection models, joint angle plots are used, respectively, to isolate the faults one by one. Finally, the reconstruction scheme is used to estimate the magnitude of the bias to recover from the faulty operation. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:764 / 777
页数:14
相关论文
共 29 条
[1]  
ANDERSON D, 1989, ASHRAE T, V95
[2]  
[Anonymous], ASHRAE T
[3]  
Comstock M.C., 1999, HL9920 PURD U RW HER
[4]  
Dexter A. L., 2001, DEMONSTRATING AUTOMA
[5]   Fault diagnosis in air-conditioning systems: A multi-step fuzzy model-based approach [J].
Dexter, AL ;
Ngo, D .
HVAC&R RESEARCH, 2001, 7 (01) :83-102
[6]   Joint diagnosis of process and sensor faults using principal component analysis [J].
Dunia, R ;
Qin, SJ .
CONTROL ENGINEERING PRACTICE, 1998, 6 (04) :457-469
[7]  
Edward JJ., 1991, USERS GUIDE PRINCIPA
[8]  
Haves P, 1996, ASHRAE TRAN, V102, P519
[9]  
HEMMELBLAU DM, 1992, IFAC S ON LIN FAULT
[10]  
House John M, 2001, ASHRAE Transactions, V107, P858