Robust Control Design for High-Power Density PV Converters in Weak Grids

被引:20
作者
Amouzegar Ashtiani, Nima [1 ]
Azizi, S. Mohsen [2 ,3 ]
Khajehoddin, S. Ali [1 ]
机构
[1] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 1H9, Canada
[2] New Jersey Inst Technol, Engn Technol Dept, Newark, NJ 07102 USA
[3] New Jersey Inst Technol, Dept Elect & Comp Engn, Newark, NJ 07102 USA
关键词
Robustness; Delays; Uncertainty; Control systems; Harmonic analysis; Oscillators; Voltage control; Current control; dc-link control; high-power density converters; photovoltaic (PV) application; robust control; weak grid; IMPROVED CONTROL STRATEGY; VOLTAGE-SOURCE INVERTERS; PREDICTIVE CONTROL; IMPLEMENTATION; COMPENSATION; OPTIMIZATION; SYSTEM;
D O I
10.1109/TCST.2018.2867212
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper proposes a robust current controller (CC) and dc-link voltage controller based on mu-synthesis and H-infinity method, respectively, for a single-phase photovoltaic (PV) converter with an LCL-filter under weak grid operation. The mu-synthesis CC guarantees system robustness against weak grid uncertainties such as grid impedance variations and voltage harmonics. Moreover, the controller compensates the system delays arising from the calculation, pulsewidth modulation, and zero order hold, as well as delay uncertainties. The CC only uses the grid current feedback which eliminates the requirement for additional loops or state measurements utilized in partial or full state-feedback systems. In addition, the H-infinity dc-link voltage controller minimizes the bus voltage fluctuations caused by variations of PV system power generation. Also, the controller ensures system robustness against such power variations, which conventional controllers fail to perform. Moreover, power decoupling is achieved by the control system without any auxiliary circuit. In addition, the stability and robust performance of the phase-locked loop in a weak grid with major impedance changes is verified. Simulation and experimental results prove the superior performance of the proposed controllers in both cases of a nominal system and a system with deviated parameters.
引用
收藏
页码:2361 / 2373
页数:13
相关论文
共 63 条
  • [1] A Modified Stationary Reference Frame-Based Predictive Current Control With Zero Steady-State Error for LCL Coupled Inverter-Based Distributed Generation Systems
    Ahmed, Khaled H.
    Massoud, Ahmed M.
    Finney, Stephen J.
    Williams, Barry W.
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (04) : 1359 - 1370
  • [2] Alcala J., 2010, 2010 Proceedings of the 12th IEEE International Power Electronics Congress, P46, DOI 10.1109/CIEP.2010.5598898
  • [3] Dynamic Phasor Model Predictive Control of Switched Mode Power Converters
    Almer, Stefan
    Mariethoz, Sebastien
    Morari, Manfred
    [J]. IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, 2015, 23 (01) : 349 - 356
  • [4] [Anonymous], 2003, IEEE Std 181-2003, P1, DOI DOI 10.1109/IEEESTD.2003.94285
  • [5] Ashtinai N.A., 2016, 2016 IEEE ENERGY CON, P1
  • [6] Ashtinai NA, 2017, IEEE ENER CONV, P58, DOI 10.1109/ECCE.2017.8095761
  • [7] Robust multivariable control design for HVDC back to back schemes
    Aten, M
    Werner, H
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (06) : 761 - 767
  • [8] Resonant Current Controller With Enhanced Transient Response for Grid-Tied Inverters
    Busada, Claudio A.
    Gomez Jorge, Sebastian
    Solsona, Jorge A.
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (04) : 2935 - 2944
  • [9] Buso S, 2006, Lectures on Power Electronics, DOI [10.2200/S00047ED1V01Y200609PEL002, DOI 10.2200/S00047ED1V01Y200609PEL002, 10.2200/S00047ED1V01Y200609PEL002.]
  • [10] A Time Delay Compensation Method Based on Area Equivalence For Active Damping of an LCL-Type Converter
    Chen, Chen
    Xiong, Jian
    Wan, Zhiqiang
    Lei, Ji
    Zhang, Kai
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (01) : 762 - 772