Using gold sequences to improve the performance of correlation based islanding detection

被引:5
作者
Reynen, Mike B. [1 ]
Osman, Ahmed H. [2 ]
Malik, Om P. [1 ]
机构
[1] Univ Calgary, Dept Elect & Comp Engn, Calgary, AB T2N 1N4, Canada
[2] Amer Univ Sharjah, Dept Elect Engn, Sharjah, U Arab Emirates
关键词
Distributed generation; Islanding detection; Islanding; Correlation; PN sequence; PROTECTION; SYSTEMS; SCHEME;
D O I
10.1016/j.epsr.2009.11.006
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
One of the problems encountered when connecting distributed generators to a distribution system is the possibility of islanded operation. Traditionally this has been prevented through the application of passive under/over voltage and frequency relays which are triggered if the island contains mismatched amounts of active and/or reactive power. respectively Various active techniques which reduce the power mismatch required for operation of the passive relays have been developed. These active techniques may fail to detect islanding in multiple generator islands if all the generators do not have identical active anti-islanding strategies An islanding detection technique based on the correlation between disturbances in system voltage and a pseudo-random sequence used to perturb the generator's output was developed for use in islands where generators may have different anti-islanding strategies Previous investigations have always used pseudo-random sequences from the maximal length family of sequences It is demonstrated in this paper that using either a Gold or Kasami sequence instead of a maximal length sequence can improve the performance of the correlation technique (C) 2009 Elsevier B V. All rights reserved.
引用
收藏
页码:733 / 738
页数:6
相关论文
共 14 条
[1]  
[Anonymous], 1983, DIGITAL COMMUNICATIO
[2]  
[Anonymous], 1547 IEEE
[3]  
Bower W., 2002, SAND20023591 SAND NA
[4]   Development of adaptive protection scheme for distribution systems with high penetration of distributed generation [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :56-63
[5]  
FUANGFOO P, 2007, POW EN SOC GEN M
[6]   Micro-grid autonomous operation during and subsequent to islanding process [J].
Katiraei, F ;
Iravani, AR ;
Lehn, PW .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :248-257
[7]  
Perales M. A., 2003, IEEE Power Electronics Letters, V1, P104, DOI 10.1109/LPEL.2004.825553
[8]  
REYNEN M, 2009, THESIS U CALGARY
[9]   Determining the relative effectiveness of islanding detection methods using phase criteria and nondetection zones [J].
Ropp, ME ;
Begovic, M ;
Rohatgi, A ;
Kern, GA ;
Bonn, RH ;
Gonzalez, S .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2000, 15 (03) :290-296
[10]   Detection of islanding of multiple dispersed photovoltaic power systems [J].
Tsukamoto, O ;
Yamagishi, K .
SOLAR ENERGY, 1996, 58 (1-3) :9-15