共 50 条
Earth return admittance impact on crossbonded underground cables
被引:3
|作者:
Magalhaes, Antonio P. C.
[1
]
Lima, Antonio C. S.
[1
]
Correia de Barros, Maria Teresa
[2
]
机构:
[1] Univ Fed Rio de Janeiro, Rio De Janeiro, Brazil
[2] Univ Lisbon, Inst Super Tecn, Lisbon, Portugal
关键词:
Electromagnetic transients;
Underground cables;
Ground return parameters;
CLOSED-FORM EXPRESSIONS;
DIFFERENT FORMULATIONS;
TRANSIENT ANALYSIS;
PROPAGATION;
IMPEDANCES;
FREQUENCY;
IMPLEMENTATION;
LINES;
D O I:
10.1016/j.epsr.2021.107351
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
Typically, the modeling of underground cables systems for electromagnetic transient simulations is carried out disregarding the effects of the ground return admittance. However, recent studies have presented precise models for the representation of the earth return admittance and demonstrated the importance of considering its effects on transient overvoltages along the cable and at sheaths crossbonding, especially if short minor sections are involved. In this paper, a study on the effects of the ground return admittance when considering an underground cross-bonded cable system is presented for 1 km and 300 m for the minor section length where the effects of earth return admittance are to be more pronounced. The inclusion of the ground-return admittance leads to a higher damping, which indicates that the conventional approach may lead to over conservative results.