A Novel Double Terminal Traveling Wave Fault Location Method not Influenced by Wave Speed

被引:0
|
作者
Wu Zhihua [1 ]
Li Zewen [1 ]
Qin Xiao'an [1 ]
Hu Xiang [1 ]
Zeng Xiangjun [1 ]
机构
[1] Changsha Univ Sci & Technol, Sch Elect & Informat Engn, Changsha 410076, Hunan, Peoples R China
关键词
fault location; traveling wave; location accuracy;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Quick and accurate location of faults is the basic task of fault location as well as an important research subject in power system relay protection. The traveling wave principles of double terminal fault locating method is described, and the main causes of the generation of errors in actual application are investigated. A novel double terminal fault locating method is presented based on the existing fault locating method. The arriving intervals of the travelling wave from the fault location, reflected wave from fault location and reflected wave from opposite fats are recorded. The new fault location method is applied in Zhuzhou power grid, and the maths show that it has high Location accuracy.
引用
收藏
页码:748 / 751
页数:4
相关论文
共 50 条
  • [1] Research on an improved double-terminal traveling wave fault location method for UHVDC project
    Sun G.
    Wang Y.
    Xue F.
    Li M.
    Dong J.
    Liang W.
    Le J.
    1600, Power System Protection and Control Press (48): : 113 - 120
  • [2] Single terminal method of traveling wave fault location in distribution network
    North China Electric Power University, Baoding 071003, China
    Dianli Xitong Zidonghue, 2009, 7 (93-96):
  • [3] A novel fault location method for hybrid lines based on traveling wave
    Xie, Liwei
    Luo, Longfu
    Ma, Junjie
    Li, Yong
    Zhang, Mingmin
    Zeng, Xiangjun
    Cao, Yijia
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 141
  • [4] A Novel Two-terminal Asynchronous Fault Location Method Based on Exchange Traveling Wave Information in Fault Section
    Luo, Xunhua
    Wu, Jingyang
    Jia, Pengjun
    Deng, Zhiming
    2023 IEEE PES 15TH ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE, APPEEC, 2023,
  • [5] A double-terminal fault location method for UHVDC transmission lines based on traveling wave mode decomposition
    Wang H.
    Zhou N.
    Wang W.
    Wang Q.
    Yu D.
    Zhou D.
    Lü Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (01): : 109 - 120
  • [6] A Double-Terminal Traveling-Wave-Based Method Using Novel Noncontact Sensors for Fault Location in Transmission Cable Lines
    Zhang, Ming
    Zhao, Kun
    Yan, Yuan
    Lu, Yuxin
    Yang, Saike
    Wang, Li
    Li, Hongjie
    IEEE ACCESS, 2021, 9 : 80797 - 80805
  • [7] Traveling Wave Fault Location Method Analysis and Prospect
    Liao, Hongyu
    Yuan, Yanlei
    Liu, Le
    Yu, Pengfei
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1419 - 1423
  • [8] A novel method of tower fault location using natural frequencies of traveling wave
    School of Electrical Engineering, Wuhan University, Wuhan 430072, China
    不详
    Dianli Xitong Zidonghue, 5 (78-82+102):
  • [9] Study of fault locating for transmission line double terminal traveling waves unrelated to wave speed
    Yin, Xiao-Guang
    Song, Lin-Lin
    You, Zhi
    Zhu, Zi-Zhao
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2011, 39 (01): : 35 - 39
  • [10] A new method of single terminal traveling wave location based on characteristic of superposition of forward traveling wave and backward traveling wave
    Tian, Xincui
    Shu, Hongchun
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 133