Performance analysis of different flow types of internally-cooled membrane-based liquid desiccant dehumidifiers

被引:6
作者
Li, Wei [1 ]
Yao, Ye [1 ]
机构
[1] Shanghai Jiao Tong Univ, Sch Mech Engn, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
Dehumidification; Internally-cooled; Membrane; Flow types; Liquid desiccant; AIR-CONDITIONING SYSTEM; MASS-TRANSFER; 3-FLUID; HEAT; CONVECTION;
D O I
10.1016/j.energy.2021.120597
中图分类号
O414.1 [热力学];
学科分类号
摘要
It is well known that internally-cooled membrane-based liquid desiccant dehumidifier (IMLDD) has better dehumidification efficiency than adiabatic membrane-based liquid desiccant dehumidifier (AMLDD). The flow directions of air, solution, and cooling water in the IMLDD can dramatically affect dehumidification and cooling performance. In this paper, the mathematical models for the IMLDD of ten flow types were developed and validated experimentally. Based on the validated model, the differences of air temperature and humidity among various flow types of the IMLDD were investigated, and the effects of operating conditions on the performance of different flow types were also studied thoroughly. The main conclusions of this paper include the following: The flow types of IMLDD have different average temperature and humidity differences between air and solution. Under different operating conditions, the IMLDD of flow type b4 always has a maximum total cooling capacity. The moisture removal rate of flow type b4 is up to 8.2% greater than flow type a2 of worst performance, and for the sensible cooling capacity, the flow type b4 is up to 5 times flow type a2. This paper can help researchers and engineers to choose the appropriate form of the IMLDD according to inlet conditions. (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:14
相关论文
共 29 条
[1]   Performance testing of a novel 3-fluid liquid-to-air membrane energy exchanger (3-fluid LAMEE) under desiccant solution regeneration operating conditions [J].
Abdel-Salam, Mohamed R. H. ;
Besant, Robert W. ;
Simonson, Carey J. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 95 :773-786
[2]   Design and testing of a novel 3-fluid liquid-to-air membrane energy exchanger (3-fluid LAMEE) [J].
Abdel-Salam, Mohamed R. H. ;
Besant, Robert W. ;
Simonson, Carey J. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 92 :312-329
[3]  
[Anonymous], 2018 GLOBAL STATUS R
[4]  
[Anonymous], 2012, BP ENERGY OUTLOOK 20
[5]   Experimental study of a membrane-based dehumidification cooling system [J].
Chen, Ziwei ;
Zhu, Jie ;
Bai, Hongyu ;
Yan, Yuying ;
Zhang, Lizhi .
APPLIED THERMAL ENGINEERING, 2017, 115 :1315-1321
[6]  
Chiang YC, 2019, ENERGY, V191
[7]   CORRELATING EQUATION FOR FORCED-CONVECTION FROM GASES AND LIQUIDS TO A CIRCULAR-CYLINDER IN CROSS-FLOW [J].
CHURCHILL, SW ;
BERNSTEIN, M .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1977, 99 (02) :300-306
[8]   Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design [J].
Conde, MR .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2004, 43 (04) :367-382
[9]   Performance enhancement of solar-assisted liquid desiccant dehumidifiers using super-hydrophilic surface [J].
Dong, Chuanshuai ;
Qi, Ronghui ;
Zhang, Lizhi ;
Lu, Lin .
ENERGY AND BUILDINGS, 2019, 199 :461-471
[10]   Natural convection liquid desiccant loop as an auxiliary air conditioning system: investigating the operational parameters [J].
Fazilati, Mohammad Ali ;
Alemrajabi, Ali Akbar ;
Sedaghat, Ahmad .