Experimental Study on Utilization of Heat Pipe Heat Exchanger for Energy Conservation of Air Conditioning System in a Hospitals and its Techno-Economic Feasibility

被引:4
作者
Hakim, Imansyah Ibnu [1 ]
Putra, Nandy [1 ]
Sukarno, Ragil [1 ]
Audi, Muhammad Rifqi [1 ]
Rachman, Fadhil Fuad [1 ]
机构
[1] Univ Indonesia, Dept Mech Engn, Appl Heat Transfer Res Grp, Kampus UI, Depok 16424, Indonesia
来源
4TH INTERNATIONAL TROPICAL RENEWABLE ENERGY CONFERENCE (I-TREC 2019) | 2020年 / 2255卷
关键词
Heat pipe heat exchanger; effectiveness; energy saving; payback periods; WASTE HEAT; HVAC;
D O I
10.1063/5.0014138
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
With its growing economy and population, the need of energy for facilities in Indonesia increases, particularly in a hospital. Energy needs for the air conditioning system in the hospital is very large, so that the effort to use energy efficiently becomes very important. The purpose of this study is to investigate the influence of heat pipe heat exchanger (HPHE) applied to the ducting of air conditioning system to effectiveness and energy recovery. This study will also focus on economic analysis to determine the feasibility of HPHE applied in the air conditioning system. The HPHE used in this research is varied in 1, 2, and 3 modules which consists of 12 heat pipes each module are arranged in staggered configuration. Air inlet temperature in the evaporator section is varied of 28, 30, 35, and 40 degrees C, and air inlet velocity varied of 1.5, 2.0, 2.5 m/s. Material, production, and installation cost of HPHE in 1, 2, and 3 modules are calculated and compared with electricity energy saving to know how long of time to recover the investment of HPHE. The results show that the maximum effectiveness of 40.25 % obtained at 3 modules of HPHE, with air inlet temperature of 40 degrees C, and the inlet air velocity of 1.5 m/s. It is also found that a maximum heat recovery of 400.54 Watts and annual cost saving of IDR 1.410.205 per year is found when the inlet temperature of 40 degrees C, air velocity of 2.5 m/s, and with three modules installed into the ducting of the air conditioning system. With energy saving of IDR 723,190 per year on air inlet temperature 40 degrees C and air velocity 2.5 m/s, HPHE with 1 module has a shorter payback period than HPHE with 2 and 3-modules.
引用
收藏
页数:6
相关论文
共 40 条
  • [21] Study on Performance Analysis of Earth-Air-Pipe Heat Exchanger as Passive Cooling and Heating System
    Verma, Mahendra Kumar
    Bansal, Vikas
    Rana, Kunj Bihari
    ADVANCES IN FLUID AND THERMAL ENGINEERING, 2019, : 821 - 836
  • [22] Experimental Investigation of Using Liquid Suction Heat Exchanger with Condensed Cold-Water on the Performance of Air Conditioning System
    Homon, Phairoj
    Chantawong, Preeda
    Khedari, Joseph
    INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2022, 40 (02) : 390 - 396
  • [23] Analysis of the Energy-Saving Effect of a Novel Central Air-Conditioning System with an Internal Heat Exchanger in Summer
    Deng, Sensen
    Wang, Dong
    Zhang, Kangkang
    Li, Mengxue
    Lu, Yuehong
    SUSTAINABILITY, 2024, 16 (13)
  • [24] The application of heat pipe heat exchangers to improve the air quality and reduce the energy consumption of the air conditioning system in a hospital ward-A full year model simulation
    Ahmadzadehtalatapeh, M.
    Yau, Y. H.
    ENERGY AND BUILDINGS, 2011, 43 (09) : 2344 - 2355
  • [25] Performance study of the indirect evaporative air cooler and heat recovery exchanger in air conditioning system during the summer and winter operation
    Anisimov, Sergey
    Pandelidis, Demis
    Jedlikowski, Andrzej
    ENERGY, 2015, 89 : 205 - 225
  • [26] Experimental Study on Energy Saving of Fluidized Bed Dryer with Self-Excited Mode Oscillating-Flow Heat Pipe Heat Exchanger
    Chai, Benyin
    Li, Xuanyou
    Zhou, Shenjie
    Liu, Dengying
    Shao, Min
    Peng, Lihua
    INTERNATIONAL JOURNAL OF FOOD ENGINEERING, 2010, 6 (02):
  • [27] Low-Grade heat utilization: Techno-Economic assessment of a hybrid CO2 heat pump and Organic Rankine Cycle system integrated with photovoltaics and thermal storage
    Liaqat, Kashif
    Soleimani, Shima
    Schaefer, Laura
    APPLIED THERMAL ENGINEERING, 2025, 268
  • [28] Energy-saving heat pump-assisted extractive-azeotropic dividing wall column with heat exchanger network for separating acetonitrile and water: A techno-economic and inherent safety investigation
    Zhai, Jian
    Chen, Xin
    Xie, Hongfei
    Sun, Xiaoqing
    Hu, Mingyang
    Dang, Mingyan
    Zhao, Ping
    Liu, Yuliang
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2023, 173 : 178 - 190
  • [29] The use of a double heat pipe heat exchanger system for reducing energy consumption of treating ventilation air in an operating theatre- A full year energy consumption model simulation
    Yau, Y. H.
    ENERGY AND BUILDINGS, 2008, 40 (05) : 917 - 925
  • [30] Experimental Study to Investigate the Effect of Backfilling Materials on Thermal Performance of Ground Air Heat Exchanger System
    Agrawal, Kamal Kumar
    Misra, Rohit
    Das Agrawal, Ghanshyam
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2020, 12 (02)