Experimental Study on Utilization of Heat Pipe Heat Exchanger for Energy Conservation of Air Conditioning System in a Hospitals and its Techno-Economic Feasibility

被引:4
|
作者
Hakim, Imansyah Ibnu [1 ]
Putra, Nandy [1 ]
Sukarno, Ragil [1 ]
Audi, Muhammad Rifqi [1 ]
Rachman, Fadhil Fuad [1 ]
机构
[1] Univ Indonesia, Dept Mech Engn, Appl Heat Transfer Res Grp, Kampus UI, Depok 16424, Indonesia
来源
4TH INTERNATIONAL TROPICAL RENEWABLE ENERGY CONFERENCE (I-TREC 2019) | 2020年 / 2255卷
关键词
Heat pipe heat exchanger; effectiveness; energy saving; payback periods; WASTE HEAT; HVAC;
D O I
10.1063/5.0014138
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
With its growing economy and population, the need of energy for facilities in Indonesia increases, particularly in a hospital. Energy needs for the air conditioning system in the hospital is very large, so that the effort to use energy efficiently becomes very important. The purpose of this study is to investigate the influence of heat pipe heat exchanger (HPHE) applied to the ducting of air conditioning system to effectiveness and energy recovery. This study will also focus on economic analysis to determine the feasibility of HPHE applied in the air conditioning system. The HPHE used in this research is varied in 1, 2, and 3 modules which consists of 12 heat pipes each module are arranged in staggered configuration. Air inlet temperature in the evaporator section is varied of 28, 30, 35, and 40 degrees C, and air inlet velocity varied of 1.5, 2.0, 2.5 m/s. Material, production, and installation cost of HPHE in 1, 2, and 3 modules are calculated and compared with electricity energy saving to know how long of time to recover the investment of HPHE. The results show that the maximum effectiveness of 40.25 % obtained at 3 modules of HPHE, with air inlet temperature of 40 degrees C, and the inlet air velocity of 1.5 m/s. It is also found that a maximum heat recovery of 400.54 Watts and annual cost saving of IDR 1.410.205 per year is found when the inlet temperature of 40 degrees C, air velocity of 2.5 m/s, and with three modules installed into the ducting of the air conditioning system. With energy saving of IDR 723,190 per year on air inlet temperature 40 degrees C and air velocity 2.5 m/s, HPHE with 1 module has a shorter payback period than HPHE with 2 and 3-modules.
引用
收藏
页数:6
相关论文
共 40 条
  • [1] Energy saving via Heat Pipe Heat Exchanger in air conditioning applications "experimental study and economic analysis"
    Abdelaziz, Gamal B.
    Abdelbaky, M. A.
    Halim, M. A.
    Omara, M. E.
    Elkhaldy, I. A.
    Abdullah, A. S.
    Omara, Z. M.
    Essa, F. A.
    Ali, Aml
    Sharshir, Swellam W.
    El-Said, Emad M. S.
    Bedair, Ahmed G.
    Kabeel, A. E.
    JOURNAL OF BUILDING ENGINEERING, 2021, 35
  • [2] Experimental study on a pulsating heat pipe heat exchanger for energy saving in air-conditioning system in summer
    Yang, Honghai
    Wang, Jun
    Wang, Ning
    Yang, Fengchang
    ENERGY AND BUILDINGS, 2019, 197 : 1 - 6
  • [3] Experimental study on the parallel-flow heat pipe heat exchanger for energy saving in air conditioning
    Shen, Chao
    Zhang, Bowen
    Zhang, Dongwei
    Zhang, Yizhe
    Wei, Shen
    Yang, Shaolun
    JOURNAL OF BUILDING ENGINEERING, 2023, 75
  • [4] A study of secondary heat recovery efficiency of a heat pipe heat exchanger air conditioning system
    Wang, Haitao
    Zhou, Shunbao
    Wei, Zhongshi
    Wang, Ren
    ENERGY AND BUILDINGS, 2016, 133 : 206 - 216
  • [6] Optimizing the performance of the air conditioning system using an innovative heat pipe heat exchanger
    Eidan, Adel A.
    Alshukri, Mohammed J.
    Al-fahham, Mohamed
    AlSahlani, Assaad
    Abdulridha, Dhurgham M.
    CASE STUDIES IN THERMAL ENGINEERING, 2021, 26
  • [7] Theoretical energy saving analysis of air conditioning system using heat pipe heat exchanger for Indian climatic zones
    Jadhav, T. S.
    Lele, M. M.
    ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH, 2015, 18 (04): : 669 - 673
  • [8] THE APPLICATION OF U-SHAPE HEAT PIPE HEAT EXCHANGER TO REDUCE RELATIVE HUMIDITY FOR ENERGY CONSERVATION IN HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) SYSTEMS
    Kusumah, Aliefka Satria
    Hakim, Imansyah Ibnu
    Sukarno, Ragil
    Rachman, Fadhil Fuad
    Putra, Nandy
    INTERNATIONAL JOURNAL OF TECHNOLOGY, 2019, 10 (06) : 1202 - 1210
  • [9] EXPERIMENTAL STUDY OF MULTI-FIN HEAT PIPE HEAT EXCHANGER FOR ENERGY EFFICIENCY IN OPERATING ROOM AIR SYSTEMS
    Muhammaddiyah, Syahrul
    Winarta, Adi
    Putra, Nandy
    INTERNATIONAL JOURNAL OF TECHNOLOGY, 2018, 9 (02) : 422 - 429
  • [10] Analysis of enthalpy change with/without a heat pipe heat exchanger in a tropical air conditioning system
    Yau, Y. H.