A Novel Open-Circuit Fault Detection and Localization Scheme for Cascaded H-Bridge Stage of a Three-Stage Solid-State Transformer

被引:34
作者
Gorla, Naga Brahmendra Yadav [1 ]
Kolluri, Sandeep [1 ]
Chai, Merlin [1 ]
Panda, Sanjib Kumar [1 ]
机构
[1] Natl Univ Singapore, Dept Elect & Comp Engn, Singapore 117581, Singapore
基金
新加坡国家研究基金会;
关键词
Circuit faults; Switches; Voltage measurement; Fault detection; Switching frequency; Phase modulation; Cascaded multilevel converter (MMC); fault detection and localization; multiple switch failures; open-circuit (OC) faults; solid-state transformer (SST); MODULAR MULTILEVEL CONVERTERS; POWER BALANCE CONTROL; VOLTAGE; PROTECTION; FAILURES;
D O I
10.1109/TPEL.2019.2918148
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A three-stage solid-state transformer (SST) is a preferred replacement for line frequency transformer as it provides ancillary services in addition to stepping-up/down of grid voltages. Each active switch in SST is a potential source of failure, and a quick fault detection and isolation help in reducing the downtime. In this article, a novel fault detection and localization algorithm is proposed to localize the open-circuit (OC) faults (be it a single switch fault or multiple switch faults in multiple modules) in the cascaded H-bridge (CHB) stage of the SST. The proposed method is designed such that only one voltage sensor is needed to measure the grid-side voltage of the CHB for fault detection and localization. By comparing the estimated grid-side voltage of the CHB with the measured values, OC fault is detected. Once the fault is detected, the modulation scheme is switched from phase-shifted unipolar sinusoidal pulsewidth modulation (SPWM) to phase-shifted bipolar SPWM to localize the faults. The difference in the measured grid-side voltage of the CHB before and after each module's state change is calculated and faults are localized. The presented algorithm is substantiated using experimental results from a 1-kVA SST prototype. The main advantage of the proposed algorithm is that it requires only 2n comparisons to localize the faulty modules in a CHB with n H-bridges, which takes less than a line cycle to complete.
引用
收藏
页码:8713 / 8729
页数:17
相关论文
共 37 条
[11]  
Holdsworth B., 2002, Digital Logic Design, Vfourth
[12]  
June-Hee Lee, 2016, 2016 IEEE International Conference on Power and Energy (PECon), P473, DOI 10.1109/PECON.2016.7951608
[13]   Open-Circuit IGBT Fault Detection and Location Isolation for Cascaded Multilevel Converters [J].
Lamb, Jacob ;
Mirafzal, Behrooz .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (06) :4846-4856
[14]   Fault Detection on Multicell Converter Based on Output Voltage Frequency Analysis [J].
Lezana, Pablo ;
Aguilera, Ricardo ;
Rodriguez, Jose .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (06) :2275-2283
[15]   Fault Diagnosis and Tolerant Control of Single IGBT Open-Circuit Failure in Modular Multilevel Converters [J].
Li, Binbin ;
Shi, Shaolei ;
Wang, Bo ;
Wang, Gaolin ;
Wang, Wei ;
Xu, Dianguo .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (04) :3165-3176
[16]   Improved Fault-Tolerant Method and Control Strategy Based on Reverse Charging for the Power Electronic Traction Transformer [J].
Liu, Jianqiang ;
Zhao, Nan .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (03) :2672-2682
[17]   Voltage Balance Control Based on Dual Active Bridge DC/DC Converters in a Power Electronic Traction Transformer [J].
Liu, Jianqiang ;
Yang, Jingxi ;
Zhang, Jiepin ;
Nan, Zhao ;
Zheng, Qionglin .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2018, 33 (02) :1696-1714
[18]   A Literature Review of IGBT Fault Diagnostic and Protection Methods for Power Inverters [J].
Lu, Bin ;
Sharma, Santosh K. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2009, 45 (05) :1770-1777
[19]  
Mtepele KO, 2016, INT CONF POW ELECTR, P75, DOI 10.1109/CIEP.2016.7530734
[20]  
Peng F. Z, 2018, P 23 ANN APPL POW EL, P1602