Influence of building envelope characteristics on the effectiveness of PMV-based controls for schools located in Saudi Arabia

被引:9
作者
Alaidroos, Alaa [1 ]
Almaimani, Ayad [2 ]
Krarti, Moncef [3 ]
Qurnfulah, Emad [2 ]
Tiwari, Alok [2 ]
机构
[1] King Abdulaziz Univ, Architectural Engn Dept, Jeddah, Saudi Arabia
[2] King Abdulaziz Univ, Fac Architecture & Planning, Jeddah, Saudi Arabia
[3] Univ Colorado, Bldg Syst Program, Boulder, CO 80309 USA
关键词
indoor thermal comfort; PMV-based controls; energy efficiency; school buildings; Saudi Arabia; MEAN RADIANT TEMPERATURE; THERMAL COMFORT CONTROL; ENERGY-CONSUMPTION; STRATEGIES; IMPACT;
D O I
10.1177/1420326X221107504
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper summarizes the results of a comprehensive analysis to investigate the performance of both thermal comfort-based and temperature-based controls for schools in harsh hot climates of Saudi Arabia. The analysis considers the impact of building envelope characteristics including thermal insulation level of exterior walls and air leakage rate on the ability of both control options to maintain indoor thermal comfort while minimizing cooling energy consumption. The analysis utilizes a calibrated energy model for an existing Saudi school with monitored energy consumption data. The analysis results indicated that the thermal comfort-based control is able to maintain the predicted percentage of dissatisfied (PPD) value at 5% throughout the year for any combination of the exterior wall's R-value and air infiltration rate unlike the case of the temperature-based controls that do not maintain acceptable indoor thermal comfort conditions. However, the thermal comfort-based controls consume more cooling energy than the temperature-based controls. The analysis also revealed that the difference between the annual cooling energy of the PMV-based control and the temperature-based controls increases almost linearly with the cooling degree days of the site where the school is located. The analysis results indicate that acceptable indoor thermal comfort levels can be achieved using temperature-based controls when optimal temperature set points are used.
引用
收藏
页码:2411 / 2429
页数:19
相关论文
共 48 条
[1]   Experimental analysis of air tightness in Mediterranean buildings using the fan pressurization method [J].
Alfano, F. R. d'Ambrosio ;
Dell'Isola, M. ;
Ficco, G. ;
Tassini, F. .
BUILDING AND ENVIRONMENT, 2012, 53 :16-25
[2]   On the measurement of the mean radiant temperature and its influence on the indoor thermal environment assessment [J].
Alfano, Francesca Romana d'Ambrosio ;
Dell'Isola, Marco ;
Palella, Boris Igor ;
Riccio, Giuseppe ;
Russi, Aldo .
BUILDING AND ENVIRONMENT, 2013, 63 :79-88
[3]   Energy consumption and efficiency in buildings: current status and future trends [J].
Allouhi, A. ;
El Fouih, Y. ;
Kousksou, T. ;
Jamil, A. ;
Zeraouli, Y. ;
Mourad, Y. .
JOURNAL OF CLEANER PRODUCTION, 2015, 109 :118-130
[4]  
American Society of Heating Refrigerating and Air-Conditioning Engineers. Standards Committee, 2013, 552013 ANSIASHRAE, P1
[5]  
[Anonymous], 2012, Regents of the University of California, Berkeley
[6]  
ASHRAE, 2014, GUID 14 2014 MEAS EN
[7]   Effect of solar radiation on human thermal comfort in a tropical climate [J].
Chaiyapinunt, Somsak ;
Khamporn, Nopparat .
INDOOR AND BUILT ENVIRONMENT, 2021, 30 (03) :391-410
[8]   Analysis on the impact of mean radiant temperature for the thermal comfort of underfloor air distribution systems [J].
Chung, Jae Dong ;
Hong, Hiki ;
Yoo, Hoseon .
ENERGY AND BUILDINGS, 2010, 42 (12) :2353-2359
[9]   Application of HVAC Systems with Control Based on PMV Index in University Buildings with Complex Topology [J].
Conceicao, Eusebio Z. E. ;
Gomes, Joao M. M. ;
Ruano, Antonio E. .
IFAC PAPERSONLINE, 2018, 51 (10) :20-25
[10]   Comparison of mean radiant and air temperatures in mechanically-conditioned commercial buildings from over 200,000 field and laboratory measurements [J].
Dawe, Megan ;
Raftery, Paul ;
Woolley, Jonathan ;
Schiavon, Stefano ;
Bauman, Fred .
ENERGY AND BUILDINGS, 2020, 206