Closed-Form Expressions for the Estimation of the Minimum Backflashover Current of Overhead Transmission Lines

被引:34
作者
Datsios, Zacharias G. [1 ]
Mikropoulos, Pantelis N. [1 ]
Tsovilis, Thomas E. [1 ]
机构
[1] Aristotle Univ Thessaloniki, Sch Elect & Comp Engn, High Voltage Lab, Thessaloniki 54124, Greece
关键词
Backflashover; EMTP; flashover; insulation coordination; lightning; overhead transmission lines;
D O I
10.1109/TPWRD.2020.2984423
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The minimum backflashover current, I-BF, of typical overhead transmission lines is estimated through ATP-EMTP simulations considering the tower ground resistance and AC voltage phase angle as parameters. Several single- and double-circuit lines are investigated with operating voltage from 66 kV to 765 kV and Basic Insulation Level from 325 kV to 1950 kV. The backflashover rate, BFR, of the investigated lines is obtained using an expression that accurately considers lightning incidence to the line for prospective currents higher than I-BF; the relevant CIGRE expression underestimates BFR. BFR can be easily estimated using solely the phase angle values corresponding to zero AC voltage of the phase conductors. Based on the I-BF and BFR results, simple expressions are introduced for the calculation of an equivalent minimum backflashover current as a function of insulator length and tower ground resistance or impulse impedance. These expressions enable straightforward estimation of BFR without the need for time-consuming simulations or laborious analytical methods adopting simplifying assumptions.
引用
收藏
页码:522 / 532
页数:11
相关论文
共 69 条
[1]  
Alipio R, 2015, 2015 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIII SIPDA), P215, DOI 10.1109/SIPDA.2015.7339314
[2]   Frequency Dependence of Soil Parameters: Effect on the Lightning Response of Grounding Electrodes [J].
Alipio, Rafael ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2013, 55 (01) :132-139
[3]   Accurate modelling of rod driven tower footing [J].
Almeida, ME ;
deBarros, MTC .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1606-1609
[4]   A method of a lightning surge analysis recommended in Japan using EMTP [J].
Ametani, A ;
Kawamura, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :867-875
[5]  
Ametani A, 2017, POWER SYSTEM TRANSIE, V2nd
[6]  
[Anonymous], 1985, IEEE T POWER AP SYST, V104, P919
[7]  
[Anonymous], 1991, CIGRE Brochure 63-Guide to Procedures for Estimating the Lightning Performance of Transmission Lines
[8]  
[Anonymous], 2008, P 43 INT U POW ENG C
[9]  
[Anonymous], 2005, EPRI AC Transmission Line Reference Book-200 kV and Above, V3rd
[10]  
[Anonymous], 2004, Technical Report IEC TR 60071-4