Thermo-Hydraulic Performance of U-Tube Borehole Heat Exchanger with Different Cross-Sections

被引:16
作者
Zhou, Aizhao [1 ]
Huang, Xianwen [1 ,2 ]
Wang, Wei [3 ]
Jiang, Pengming [1 ]
Li, Xinwei [1 ,2 ]
机构
[1] Jiangsu Univ Sci & Technol, Sch Civil & Architecture Engn, Zhenjiang 212003, Jiangsu, Peoples R China
[2] Anhui Univ Sci & Technol, Sch Architecture & Civil Engn, Huainan 232000, Peoples R China
[3] Shaoxing Univ, Sch Civil Engn, Shaoxing 312000, Peoples R China
基金
中国国家自然科学基金;
关键词
ground source heat pump; borehole heat exchange; single U-shape; tube shape; heat resistance; THERMAL-RESISTANCE; GEOTHERMAL-ENERGY; SIMULATION; GENERATION; SYSTEMS; PIPES; PUMPS;
D O I
10.3390/su13063255
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
For reducing the initial GSHP investment, the heat transfer efficiency of the borehole heat exchange (BHE) system can be enhanced to reduce the number or depth of drilling. This paper proposes a novel and simple BHE design by changing the cross-sectional shape of the U-tube to increase the heat transfer efficiency of BHEs. Specifically, in this study, we (1) verified the reliability of the three-dimensional numerical model based on the thermal response test (TRT) and (2) compared the inlet and outlet temperatures of the different U-tubes at 48 h under the premise of constant leg distance and fluid area. Referent to the circular tube, the increases in the heat exchange efficiencies of the curved oval tube, flat oval tube, semicircle tube, and sector tube were 13.0%, 19.1%, 9.4%, and 14.8%, respectively. (3) The heat flux heterogeneity of the tubes on the inlet and outlet sides of the BHE, in decreasing order, is flat oval, semicircle, curved oval, sector, and circle shapes. (4) The temperature heterogeneity of the borehole wall in the BHE in decreasing order is circle, sector, curved oval, flat oval, and semicircle shapes. (5) Under the premise of maximum leg distance, referent to the heat resistance of the tube with a circle shape at 48 h, the heat exchange efficiency of the curved oval, flat oval, semicircle, and sector tubes increased 12.6%, 17.7%, 10.3%, and 7.8%, respectively. (6) We found that the adjustments of the leg distance and the tube shape affect the heat resistance by about 25% and 12%, respectively. (7) The flat-oval-shaped tube at the maximum leg distance was found to be the best tube design for BHEs.
引用
收藏
页数:20
相关论文
共 48 条
[1]   Analysis of the thermal and hydraulic performance of the sector-by-sector helically coiled tube heat exchangers as a new type of heat exchangers [J].
Abu-Hamdeh, Nidal H. ;
Bantan, Rashad A. R. ;
Tlili, Iskander .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2020, 150
[2]  
[Anonymous], 2009, 503662009 GB
[3]   The Impact on System Performance When Renovating a Multifamily Building Stock in a District Heated Region [J].
Blomqvist, Stefan ;
La Fleur, Lina ;
Amiri, Shahnaz ;
Rohdin, Patrik ;
Odlund, Louise .
SUSTAINABILITY, 2019, 11 (08)
[4]   Techno-economic and spatial analysis of vertical ground source heat pump systems in Germany [J].
Blum, Philipp ;
Campillo, Gisela ;
Koelbel, Thomas .
ENERGY, 2011, 36 (05) :3002-3011
[5]   Characteristics of heat fluxes in subsurface shallow depth soil layer as a renewable thermal source for ground coupled heat pumps [J].
Brys, Krystyna ;
Brys, Tadeusz ;
Sayegh, Marderos Ara ;
Ojrzynska, Hanna .
RENEWABLE ENERGY, 2020, 146 :1846-1866
[6]   Subsurface shallow depth soil layers thermal potential for ground heat pumps in Poland [J].
Brys, Krystyna ;
Brys, Tadeusz ;
Sayegh, Marderos Ara ;
Ojrzynska, Hanna .
ENERGY AND BUILDINGS, 2018, 165 :64-75
[7]   Review on greenhouse microclimate and application: Design parameters, thermal modeling and simulation, climate controlling technologies [J].
Choab, Noureddine ;
Allouhi, Amine ;
El Maakoul, Anas ;
Kousksou, Tarik ;
Saadeddine, Said ;
Jamil, Abdelmajid .
SOLAR ENERGY, 2019, 191 :109-137
[8]   Three-dimensional numerical model of heat losses from district heating network pre-insulated pipes buried in the ground [J].
Danielewicz, J. ;
Sniechowska, B. ;
Sayegh, M. A. ;
Fidorow, N. ;
Jouhara, H. .
ENERGY, 2016, 108 :172-184
[9]   Free surface vortices at hydropower intakes: - A state-of-the-art review [J].
Domfeh, Martin Kyereh ;
Gyamfi, Samuel ;
Amo-Boateng, Mark ;
Andoh, Robert ;
Ofosu, Eric Antwi ;
Tabor, Gavin .
SCIENTIFIC AFRICAN, 2020, 8
[10]   Potential of geothermal heat exchangers for office building climatisation [J].
Eicker, Ursula ;
Vorschulze, Christoph .
RENEWABLE ENERGY, 2009, 34 (04) :1126-1133