Passive cooling and natural ventilation by the windcatcher (Badgir): An experimental and simulation study of indoor air quality, thermal comfort and passive cooling power

被引:48
作者
Nejat, Payam [1 ,2 ]
Ferwati, M. Salim [3 ]
Calautit, John [4 ]
Ghahramani, Ali [5 ]
Sheikhshahrokhdehkordi, Mohammadamin [6 ]
机构
[1] Adv Bldg & Environm Res ABER Ctr, Johor Baharu, Malaysia
[2] Univ Teknol Malaysia, Fac Civil Engn, Johor Baharu, Malaysia
[3] Univ Qatar, Dept Architecture & Urban Planning, Fac Engn, Doha, Qatar
[4] Univ Nottingham, Dept Architecture & Built Environm, Fac Engn, Nottingham, England
[5] Natl Univ Singapore, Dept Bldg, Singapore, Singapore
[6] Univ N Carolina, Dept Mech Engn & Engn Sci, Charlotte, NC 28223 USA
关键词
Natural ventilation; Badgir; Windcatcher; Wing wall; Passive cooling; Indoor air quality; Thermal comfort; 2-SIDED WIND-CATCHER; CFD SIMULATION; PERFORMANCE; BUILDINGS; FLOW; DESIGN; ROOM; TOWER; ENVIRONMENT; VALIDATION;
D O I
10.1016/j.jobe.2021.102436
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The upper wing wall can be integrated into the windcatcher to prevent direct solar and rain penetration. The impact of this combination was not considered in previous studies. Moreover, analyzing adaptive thermal comfort is another gap that was not addressed by preceding windcatcher studies, particularly for the tropical climate. Therefore, the current research aims to evaluate a two-sided windcatcher incorporated with the upper wing wall from two views: indoor air quality (IAQ) and adaptive thermal comfort. A small-scale model was tested in the wind tunnel. Next, CFD models were validated against experimental data with a good agreement between the two methods. Windcatchers with different upper wing wall lengths ranging between 10 cm and 50 cm were assessed. The results showed that the length increase led to a slight increase in the ventilation rate, and the best performance was seen in the 50 cm configuration. Subsequently, IAQ and adaptive thermal comfort were evaluated at different wind speeds of this climate. The results demonstrated that even in wind speeds below the annual average (2.5 m/s), the windcatcher performance can still satisfy IAQ parameters such as airflow rate and air change rate, recommend by CIBSE Guide A. In addition, based on the simulated conditions the results showed that wind speed from 2.5 m/s to 4 m/s could provide thermal comfort within 50%-80% of the ventilated space. Finally, the estimation of passive cooling power showed that windcatcher could provide a maximum (9.6 kW) cooling power if the wind speed is at 4 m/s and outdoor temperature at 23 degrees C.
引用
收藏
页数:20
相关论文
共 68 条
[1]   An experimental investigation of the thermal effect due to discharging of phase change material in a room fitted with a windcatcher [J].
Abdo, Peter ;
Huynh, B. Phuoc ;
Braytee, Ali ;
Taghipour, Rahil .
SUSTAINABLE CITIES AND SOCIETY, 2020, 61
[2]   An experimental study on the evaluation of natural ventilation performance of a two-sided wind-catcher for various wind angles [J].
Afshin, M. ;
Sohankar, A. ;
Manshadi, M. Dehghan ;
Esfeh, M. Kazemi .
RENEWABLE ENERGY, 2016, 85 :1068-1078
[3]   Towards optimal aerodynamic design of wind catchers: Impact of geometrical characteristics [J].
Alsailani, M. ;
Montazeri, H. ;
Rezaeiha, A. .
RENEWABLE ENERGY, 2021, 168 :1344-1363
[4]  
[Anonymous], 2014, INT J ENERGY TECHNOL, DOI DOI 10.1504/IJETP.2014.065036
[5]  
ANSYS Incorporated, 2019, ANSYS 19 FLUENT THEO
[6]   Natural ventilation of an isolated generic building with a windward window and different windexchangers: CFD validation, sensitivity study and performance analysis [J].
Antonio Castillo, J. ;
Huelsz, Guadalupe ;
van Hooff, Twan ;
Blocken, Bert .
BUILDING SIMULATION, 2019, 12 (03) :475-488
[7]   CFD simulation of the atmospheric boundary layer: wall function problems [J].
Blocken, Bert ;
Stathopoulos, Ted ;
Carmeliet, Jan .
ATMOSPHERIC ENVIRONMENT, 2007, 41 (02) :238-252
[8]   Development of a natural ventilation windcatcher with passive heat recovery wheel for mild-cold climates: CFD and experimental analysis [J].
Calautit, John Kaiser ;
O'Connor, Dominic ;
Tien, Paige Wenbin ;
Wei, Shuangyu ;
Pantua, Conrad Allan Jay ;
Ben Hughes .
RENEWABLE ENERGY, 2020, 160 :465-482
[9]   Numerical and experimental investigation of the indoor air quality and thermal comfort performance of a low energy cooling windcatcher with heat pipes and extended surfaces [J].
Calautit, John Kaiser ;
Tien, Paige Wenbin ;
Wei, Shuangyu ;
Calautit, Katrina ;
Hughes, Ben .
RENEWABLE ENERGY, 2020, 145 :744-756
[10]   Measurement and prediction of the indoor airflow in a room ventilated with a commercial wind tower [J].
Calautit, John Kaiser ;
Hughes, Ben Richard .
ENERGY AND BUILDINGS, 2014, 84 :367-377