Fires originating in branch-circuit NM cables due to installation damage

被引:8
作者
Babrauskas, Vytenis [1 ,2 ]
机构
[1] Fire Sci & Technol Inc, 926 Hayes Ave, San Diego, CA 92103 USA
[2] Univ Calif San Diego, La Jolla, CA 92093 USA
关键词
Dielectric strength of cables; electrical fires; forensic failure analysis; electrical installation defects; NM cables; voltage surges;
D O I
10.1177/0734904118785920
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A significant fraction of US structure fires originate in electrical wiring, and there is also reason to believe that these numbers may be systematically undercounted. The role of voltage surges and damaged insulation in creating the potential for fire is discussed. That damaged electrical insulation may lead to fire has been known for a century, yet details of the mechanisms by which this occurs have not been extensively studied. An Underwriters Laboratories study established that damage which may not appear visually striking may result in dielectric failure; such failures can be a direct cause of fire. Case histories are presented illustrating how mechanical damage associated with stapling of NM cables can result in serious fires. Reliability of branch-circuit wiring methods is discussed and possible preventive measures are described.
引用
收藏
页码:438 / 450
页数:13
相关论文
共 16 条
  • [1] Ahrens M., 2017, Home Structure Fires
  • [2] [Anonymous], INFLUENCE DAMAGE DEG
  • [3] [Anonymous], 2013, 2012 ONT EL SAF REP
  • [4] [Anonymous], REF STAND EL WIR CAB
  • [5] [Anonymous], 1901, REP COMM AW WORLDS C, V1
  • [6] Mechanisms and modes for ignition of low-voltage, PVC-insulated electrotechnical products
    Babrauskas, V
    [J]. FIRE AND MATERIALS, 2006, 30 (02) : 151 - 174
  • [7] Babrauskas V., 2003, Ignition Handbook
  • [8] Babrauskas V., 2013, FIRE SCI TECHNOL, V32, P35, DOI DOI 10.3210/FST.32.35
  • [9] Campbell R., 2017, ELECT FIRES
  • [10] Day HT., 1918, ELECT FIRE HAZARDS