Small-Disturbance Stability Limit of a Grid-Connected Wind Farm With PMSGs in the Timescale of DC Voltage Dynamics

被引:25
作者
Du, Wenjuan [1 ]
Wang, Yijun [2 ]
Wang, H. F. [1 ]
Ren, Bixing [3 ]
Xiao, Xianyong [1 ]
机构
[1] Sichuan Univ, Sch Elect Engn, Chengdu 610065, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst New Ener, Beijing 102206, Peoples R China
[3] State Grid Jiangsu Elect Power Co Ltd Res Inst, Nanjing 211103, Peoples R China
关键词
Power system stability; Wind farms; Power system dynamics; Phase locked loops; Numerical stability; Stability criteria; Small-disturbance stability; wind farm; phase locked loop (PLL); permanent magnet synchronous generator (PMSG); DC voltage dynamics; POWER CONVERTERS; OSCILLATIONS; GENERATOR;
D O I
10.1109/TPWRS.2020.3031351
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analytically derives the small-disturbance stability limit of a grid-connected wind farm with multiple PMSGs in the timescale of DC voltage dynamics. The derived stability limit reveals the mechanism about how the dynamics of DC voltage control and the PLLs may jointly affect the small-disturbance stability of the wind farm. Flagging the impact of PMSGs by a computational function, the stability limit indicates that decreasing value of flagging function or/and increasing maximum eigenvalue of network reactance matrix implies increased instability risk. Particularly, increasing the loading conditions and number of PMSGs in the wind farm or/and the length of transmission line connecting the wind farm with main grid may make the wind farm more prone to the loss of small-disturbance stability. Although the stability limit is derived under the assumption of identical dynamics of PMSGs, the derived small-disturbance stability limit can be applied to approximately assess the small-disturbance stability of the wind farm in the timescale of DC voltage dynamics, where dynamics of PMSGs may be either similar or considerably different. The approximate small-disturbance stability assessment is simple because the assessment does not need to establish the parametric model of the wind farm.
引用
收藏
页码:2366 / 2379
页数:14
相关论文
共 30 条
[1]   Active Mitigation of Subsynchronous Interactions Between PWM Voltage-Source Converters and Power Networks [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady Ibrahim ;
Xu, Wilsun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (01) :121-134
[2]  
[Anonymous], 1997, IEEE STANDARD DICT E, V6e, P1, DOI DOI 10.1109/IEEESTD.1997.85949
[3]  
[Anonymous], 2012, 2012 IEEE POW EN SOC
[4]  
[Anonymous], 2013, SENSORS 2013 IEEE, DOI [DOI 10.1109/ICSENS.2013.6688408, 10.1109/ICSENS.2013.6688408]
[5]   Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions [J].
Dong, Dong ;
Wen, Bo ;
Boroyevich, Dushan ;
Mattavelli, Paolo ;
Xue, Yaosuo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :310-321
[6]   Small-Signal Stability Limit of a Grid-Connected PMSG Wind Farm Dominated by the Dynamics of PLLs [J].
Du, Wenjuan ;
Dong, Wenkai ;
Wang, Haifeng .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2020, 35 (03) :2093-2107
[7]   Comparison of Methods to Examine Sub-Synchronous Oscillations Caused by Grid-Connected Wind Turbine Generators [J].
Du, Wenjuan ;
Ren, Bixing ;
Wang, Haifeng ;
Wang, Yang .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (06) :4931-4943
[8]   Dynamic Aggregation of Same Wind Turbine Generators in Parallel Connection for Studying Oscillation Stability of a Wind Farm [J].
Du, Wenjuan ;
Dong, Wenkai ;
Wang, Haifeng ;
Cao, Jun .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (06) :4694-4705
[9]   Subsynchronous Interactions Induced by DFIGs in Power Systems Without Series Compensated Lines [J].
Du, Wenjuan ;
Chen, Chen ;
Wang, Haifeng .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (03) :1275-1284
[10]   Modeling Type-4 Wind in Weak Grids [J].
Fan, Lingling .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2019, 10 (02) :853-864