Temperature calculation of overhead power line conductors based on CIGRE Technical Brochure 601 in Slovakia

被引:16
作者
Kanalik, Martin [1 ]
Margitova, Anastazia [1 ]
Bena, L'ubomir [1 ]
机构
[1] Tech Univ Kosice, Fac Elect Engn & Informat, Dept Elect Power Engn, Letna 9, Kosice 04200, Slovakia
关键词
Overhead power line; ACSR conductor; CIGRE Technical Brochure 601; CIGRE Technical Brochure 207; Dynamic thermal rating; Ampacity; TRANSMISSION-LINES; AMPACITY; MODEL; IEEE;
D O I
10.1007/s00202-019-00831-8
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An overhead power line is a structure used in the electric power system to transmit electrical energy. The performance of overhead power lines depends on their parameters. An important parameter of the power line in the power system is its thermal limit. This article deals with the temperature calculation of overhead power line ACSR conductors according to the methodology stated in CIGRE Technical Brochure 601: Guide for thermal rating calculations of overhead lines. The calculated temperature is also compared with the measurement under laboratory conditions and also on a real power line in the Slovakia power system. At the end of the article, the dynamic thermal rating of ACSR conductors depending on climatic conditions is also calculated. Obtained results are compared with ampacity limits for summer and winter season used by Slovak transmission system operators. The article also compares the CIGRE Technical Brochure 601 with its older version CIGRE Technical Brochure 207: Thermal behavior of overhead conductors.
引用
收藏
页码:921 / 933
页数:13
相关论文
共 28 条
[1]  
Abbott S., 2010, 45 INT U POWER ENG C, P1
[2]  
[Anonymous], 2013, 503411 STN EN
[3]  
[Anonymous], 2002, THERM BEH OV COND TE
[4]  
[Anonymous], 2010, 45 INT U POWER ENG C
[5]  
[Anonymous], 2012, 738 IEEE
[6]   Comparison between IEEE and CIGRE Thermal Behaviour Standards and Measured Temperature on a 132-kV Overhead Power Line [J].
Arroyo, Alberto ;
Castro, Pablo ;
Martinez, Raquel ;
Manana, Mario ;
Madrazo, Alfredo ;
Lecuna, Ramon ;
Gonzalez, Antonio .
ENERGIES, 2015, 8 (12) :13660-13671
[7]  
Beryozkina S., 2011, P 2011 10 INT C ENV, P1, DOI 10.1109/PTC.2011.6019252
[8]  
CIGRE, 2014, CONSIDERATIONS HIGH
[9]   Investigation on chatter stability of thin-walled parts considering its flexibility based on finite element analysis [J].
Ding, Yang ;
Zhu, Lida .
INTERNATIONAL JOURNAL OF ADVANCED MANUFACTURING TECHNOLOGY, 2018, 94 (9-12) :3173-3187
[10]   Review of dynamic line rating systems for wind power integration [J].
Fernandez, E. ;
Albizu, I. ;
Bedialauneta, M. T. ;
Mazon, A. J. ;
Leite, P. T. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 53 :80-92