An optimal/adaptive reclosing technique for transient stability enhancement under single pole tripping

被引:19
作者
Adly, Ahmed R. [1 ]
El Sehiemy, Ragab A. [2 ]
Abdelaziz, Almoataz Y. [3 ]
机构
[1] Atom Energy Author, Nucl Res Ctr, Cairo, Egypt
[2] Kafrelsheikh Univ, Kafr El Shaikh, Kafr El Sheikh, Egypt
[3] Ain Shams Univ, Fac Engn, Cairo, Egypt
关键词
Adaptive reclosure; Optimal reclosing time; Transient fault; Permanent fault; Transient stability; SCHEME;
D O I
10.1016/j.epsr.2017.06.005
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an integrated autoreclosure scheme (IAS) for transmission networks. The IAS operation is based on merging the functional advantages of the adaptive reclosing technique (ART) and the optimal reclosing technique (ORT). The ART identifies the nature of the fault, transient or a permanent fault, and determines the fault persistence time of a transient fault by analyzing the harmonic of the fault phase voltage using wavelet packet transform (WPT). The ORT is dependent on the load angle of the generators that minimizes the systems oscillation. The resulted information from the adaptive reclosing and the optimal reclosure timing units can effectively settled to achieve the optimum reclosing strategy that able to enhance power system stability. The proposed IAS is merited by an adaptive threshold level while needed information are captured from single end only. The IAS performance assessment compared to conventional reclosing schemes is carried out by using proposed voltage and speed indices. Examination of the proposed IAS is successfully achieved at different fault scenarios that involve various fault locations, inception angles, and representation of secondary arc characteristics. Added to that, the capability of the proposed scheme is confirmed considering the effects of shunt compensators, reactors and capacitors. Numerous simulation studies are emulated using MATLAB/SIMULINK on two test systems with different configurations. Simulation results indicate that the proposed reclosing method can enhance the transient stability. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:348 / 358
页数:11
相关论文
共 29 条
[1]  
Adly A.R., 2015, P 17 INT MIDDL E POW
[2]   An Accurate Technique for Discrimination between Transient and Permanent Faults in Transmission Networks [J].
Adly, Ahmed R. ;
El-Sehiemy, Ragab A. ;
Abdelaziz, Almoataz Y. ;
Kotb, Said A. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2017, 45 (04) :366-381
[3]  
Adly AR, 2016, PROCEEDINGS OF 2016 EIGHTEENTH INTERNATIONAL MIDDLE EAST POWER SYSTEMS CONFERENCE (MEPCON), P67, DOI 10.1109/MEPCON.2016.7836873
[4]   A negative sequence superimposed pilot protection technique during single pole tripping [J].
Adly, Ahmed R. ;
El Sehiemy, Ragab A. ;
Abdelaziz, Almoataz Y. .
ELECTRIC POWER SYSTEMS RESEARCH, 2016, 137 :175-189
[5]   Critical aspects on wavelet transforms based fault identification procedures in HV transmission line [J].
Adly, Ahmed R. ;
El Sehiemy, Ragab A. ;
Abdelaziz, Almoataz Youssef ;
Ayad, Nabil M. A. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (02) :508-517
[6]   Analysis of harmonics in power systems using the wavelet-packet transform [J].
Barros, Julio ;
Diego, Ramon I. .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2008, 57 (01) :63-69
[7]  
Bo Z. Q., 2009, POW EN ENG C APPEEC, P1
[8]   New concept in transmission line reclosure using high-frequency fault transients [J].
Bo, ZQ ;
Aggarwal, RK ;
Johns, AT ;
Zhang, BH ;
Ge, YZ .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1997, 144 (04) :351-356
[9]  
Chen Z., 2003, P POW ENG SOC GEN M, V4
[10]  
Frimpong E. A., 2010, INDIAN J COMPUTER SC, V1, P222