A Hybrid Islanding Detection Method Based on the Rates of Changes in Voltage and Active Power for the Multi-Inverter Systems

被引:56
作者
Seyedi, Masoumeh [1 ]
Taher, Seyed Abbas [1 ]
Ganji, Babak [1 ]
Guerrero, Josep [2 ]
机构
[1] Univ Kashan, Elect Engn Dept, Kashan 8731751167, Iran
[2] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
关键词
Islanding; Inverters; Voltage measurement; Voltage control; Switches; Resonant frequency; Power quality; Inverter-based DGs; islanding detection; rate of change of voltage; rate of change of active power; hybrid method; non-detection zone; multi DGs; STRATEGY;
D O I
10.1109/TSG.2021.3061567
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes hybrid islanding detection for inverter-based distributed generation (DG) units. Conventionally, passive islanding detection methods may fail when power mismatches are nearly zero. Also, the difficulty of setting threshold is another common problem. To overcome this drawback, a new procedure for islanding detection is proposed based on the combination of the rate of change of voltage (ROCOV) and the rate of change of active power (ROCOAP). The ROCOAP is only activated when the islanding condition is suspected by ROCOV. When the power mismatch is negligible, some high-impedance fault or non-islanding events occur, the proposed method can identify islanding, thus presenting a combination of advantages of each passive/active method. Therefore, it is useful to appropriately detect islanding situation in all-inclusive of scenarios. Consequently, the proposed method under several conditions, such as pulsating loads, pre-energized transformers have been considered. To illustrate the effectiveness of the proposed approach, various tests such as UL1741 have been investigated. Comparison analysis shows that the suggested method is more acceptable and the NDZ is reduced significantly. In addition, proper performance even for small power mismatch is illustrated by presence of variety of non-islanding events and improvement of power quality is achieved in comparison active method.
引用
收藏
页码:2800 / 2811
页数:12
相关论文
共 32 条
  • [1] [Anonymous], 2004, IEEE STANDARD 1547
  • [2] Anti-Islanding Protection of PV-Based Microgrids Consisting of PHEVs Using SVMs
    Baghaee, Hamid Reza
    Mlakic, Dragan
    Nikolovski, Srete
    Dragicevic, Tomislav
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2020, 11 (01) : 483 - 500
  • [3] Novel Islanding Detection Method for Multiple DGs Based on Forced Helmholtz Oscillator
    Bakhshi, Mohsen
    Noroozian, Reza
    Gharehpetian, Gevork B.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (06) : 6448 - 6460
  • [4] A remote islanding detection and control strategy for photovoltaic-based distributed generation systems
    Bayrak, Gokay
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2015, 96 : 228 - 241
  • [5] Prediction and Control of Transformer Inrush Currents
    Cardelli, Ermanno
    Faba, Antonio
    Tissi, Francesco
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (03)
  • [6] PWM Harmonic Signature-Based Islanding Detection for a Single-Phase Inverter With PWM Frequency Hopping
    Colombage, Kalhana
    Wang, Jiabin
    Gould, Chris
    Liu, Chaohui
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (01) : 411 - 419
  • [7] Harmonic Profile Injection-Based Hybrid Active Islanding Detection Technique for PV-VSC-Based Microgrid System
    Dhar, Snehamoy
    Dash, P. K.
    [J]. IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2016, 7 (04) : 1473 - 1481
  • [8] High impedance fault detection: A review
    Ghaderi, Amin
    Ginn, Herbert L., III
    Mohammadpour, Hossein Ali
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2017, 143 : 376 - 388
  • [9] Design consideration and performance analysis of a hybrid islanding detection method combining voltage unbalance/total harmonic distortion and bilateral reactive power variation
    Wang G.
    Gao F.
    Liu J.
    Li Q.
    Zhao Y.
    [J]. CPSS Transactions on Power Electronics and Applications, 2020, 5 (01): : 86 - 100
  • [10] Guha B., 2016, IEEE Power Energy Technol. Syst. J., V3, P143