Analysis of Temporary Overvoltages During Open-Phase Faults in Distribution Networks With Resonant Grounding

被引:40
作者
Kalyuzhny, Aaron [1 ]
机构
[1] Israel Elect Corp Ltd, IL-31000 Haifa, Israel
关键词
Open-phase faults; Petersen coil; resonant-grounded networks; temporary overvoltages; SYSTEMS; QUALITY;
D O I
10.1109/TPWRD.2014.2327074
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analyzes the temporary overvoltages (TOVs) that may appear in open-phase states in distribution networks with resonant grounding. The high overvoltages recorded during the open-phase states exceed the overvoltages corresponding to the existing theory. The detailed analytical study of the temporary overvoltages is performed. The closed-form expression of the neutral voltage is derived. The conditions for maximum phase-to-earth overvoltages are obtained. The case study for open-phase faults in the 33-kV resonantly grounded distribution network is described. The dependence of the TOVs on the number of distribution feeders, on the feeder loading, on detuning factor, on the additional damping factor, as well as on the saturation of the voltage transformers are analyzed. Remedies for the reduction of TOVs are considered. Detuning of the Petersen coil is compared with the permanent connection of the wattmetric resistance in parallel to the Petersen coil.
引用
收藏
页码:420 / 427
页数:8
相关论文
共 23 条
[1]  
[Anonymous], 2007, PET COIL CONTR REG D
[2]  
[Anonymous], 2003, SIM AN POW SYST TRAN
[3]  
[Anonymous], 1988, APPL GUID COMP CAP L
[4]   Minimising the risk of cross-country faults in systems using arc suppression coils [J].
Burgess, R. ;
Ahfock, A. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (07) :703-711
[5]   Ground Fault Temporary Overvoltages in MV Networks: Evaluation and Experimental Tests [J].
Cerretti, Alberto ;
Gatta, Fabio Massimo ;
Geri, Alberto ;
Lauria, Stefano ;
Maccioni, Marco ;
Valtorta, Giovanni .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1592-1600
[6]  
CIRED, 1998, FAULT MAN EL DISTR S
[7]  
Farnham S. B., 1941, T AM I ELECT ENG, V60, P1257
[8]  
Fuchs E. L., 2012, 8 INT C POW QUAL REL
[9]   A new deal for safety and quality on MV networks [J].
Griffel, D ;
Harmand, Y ;
Leitloff, V ;
Bergeal, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) :1428-1433
[10]   A case of abnormal overvoltages in a Petersen grounded 132-kV system caused by broken conductor [J].
Gustavsen, B ;
Walseth, JÅ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) :195-200