Retarding frosting of an air source heat pump by using vapor-bypassed evaporation technique

被引:8
作者
Fan, Chaochao [1 ]
Xiong, Tong [1 ]
Yan, Gang [1 ]
Yu, Jianlin [1 ]
Zhang, Hao [1 ,2 ]
Chu, Wenxiao [1 ]
Wang, Qiuwang [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Refrigerat & Cryogen Engn, Sch Energy & Power Engn, Xian 710049, Peoples R China
[2] Guangdong Midea Refrigerat Equipment Co Ltd, Foshan 528311, Peoples R China
关键词
Air source heat pump; Frost retardation; Vapor-bypassed evaporation; Performance improvement; DEFROSTING PERFORMANCE; CONDITIONING SYSTEM; EXCHANGER; UNIT;
D O I
10.1016/j.ijrefrig.2021.03.014
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a comparative experimental study on the frosting characteristics of an air source heat pump system that contains two operation modes, i.e., the vapor-bypassed evaporation (VB) mode and the conventional operation (CO) mode. For VB mode, a phase separator is installed inside the evaporator refrigerant circuit to bypass vapor refrigerant, which can increase the average evaporation temperature for retarding frosting by reducing refrigerant pressure drop and decreasing the area of refrigerant inferior heat transfer coefficient region (mist flow region). According to the experimental results, under H2 condition (indoor: 20/15 degrees C; outdoor: 2/1 degrees C), as the initial refrigerant mass flow rate ranges 35-45 g/s, the VB mode yields 4.30-7.06% lower frost mass, 3.9-7.3% higher average heating capacity and 6.4-10.8% higher coefficient of performance (COP) over CO mode with the frosting duration of 60 min. Moreover, under H3 condition (indoor: 20/15 degrees C; outdoor: -7/-8 degrees C), the frosting duration is set as 100 min, and the VB mode obtains 9.67% lower frost mass, 7.0% higher average heating capacity and 13.3% higher COP over CO mode. Generally, the vapor-bypassed evaporation technique has a great application potential in retarding frosting and improving performance of an air source heat pump system especially under high heating capacity or low ambient temperature conditions. (c) 2021 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:69 / 77
页数:9
相关论文
共 25 条
[1]  
[Anonymous], 2017, 5151 ISO
[2]   Application of a vapor-liquid separation heat exchanger to the air conditioning system at cooling and heating modes [J].
Chen, Jianyong ;
Ding, Rong ;
Li, Yunhai ;
Lin, Xu ;
Chen, Ying ;
Luo, Xianglong ;
Yang, Zhi .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 100 :27-36
[3]   Performances of a split-type air conditioner employing a condenser with liquid-vapor separation baffles [J].
Chen, Y. ;
Hua, N. ;
Deng, L. S. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (02) :278-289
[4]   Prediction of the frost growth and performance change of air source heat pump system under various frosting conditions [J].
Chung, Yoong ;
Yoo, Jin Woo ;
Kim, Gwi Taek ;
Kim, Min Soo .
APPLIED THERMAL ENGINEERING, 2019, 147 :410-420
[5]   Simulation study on the performance of a vapor-bypassed evaporator for heat pump applications [J].
Fan, Chaochao ;
Yan, Gang ;
Xiong, Tong ;
Yu, Jianlin .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 122 :47-58
[6]  
Han B, INT J REFRIG, V109, P180
[7]   Review of databases and predictive methods for pressure drop in adiabatic, condensing and boiling mini/micro-channel flows [J].
Kim, Sung-Min ;
Mudawar, Issam .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 77 :74-97
[8]   A study on the performance enhancement of heat pump using electric heater under the frosting condition: Heat pump under frosting condition [J].
Kwak, Kyungmin ;
Bai, Cheolho .
APPLIED THERMAL ENGINEERING, 2010, 30 (6-7) :539-543
[9]  
Li S, ENERGY BUILD, V211
[10]   A novel characteristic index for frosting suppression based on the configuration and operation of air source heat pumps [J].
Liang, Shimin ;
Wang, Wei ;
Sun, Yuying ;
Li, Zhaoyang ;
Zhao, Jihan ;
Lin, Yao ;
Deng, Shiming .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 109 :161-171