Propagation and localisation of partial discharge in transformer bushing based on ultra-high frequency technique

被引:18
作者
Jiang, Jun [1 ,2 ]
Chen, Judong [1 ]
Li, Jiansheng [3 ]
Yang, Xiaoping [4 ]
Albarracin-Sanchez, Ricardo [5 ]
Ranjan, Prem [2 ]
Zhang, Chaohai [1 ]
机构
[1] Nanjing Univ Aeronaut & Astronaut, Jiangsu Key Lab New Energy Generat & Power Conver, Nanjing, Peoples R China
[2] Univ Manchester, Sch Engn, Dept Elect & Elect Engn, Manchester, Lancs, England
[3] State Grid Jiangsu Elect Power Co Ltd, Res Inst, Nanjing, Peoples R China
[4] State Grid Jiangsu Elect Power Co Ltd, Nanjing, Peoples R China
[5] Univ Politecn Madrid UPM, Dept Elect Elect & Automat Engn & Appl Phys, Madrid, Spain
基金
中国博士后科学基金;
关键词
UHF SIGNALS; EXCITATION;
D O I
10.1049/hve2.12075
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As an essential component of power transformers, the detection and diagnosis of incipient partial discharge (PD) activities of bushings are of great significance. A 35-kV oil-impregnated paper (OIP) bushing is investigated. The bushing is modelled by coaxial theory and electromagnetic (EM) simulation. As the paths of PD-induced ultra-high frequency (UHF) signal propagating in the bushing are OIPs and oil gap, small attenuation during signal propagation is seen. Since OIP is composed of heterogeneous media compared with pure oil, there will be relatively less UHF signal leakage from OIPs, whereas more leakage from the oil gap. This leakage provides the possibility of non-contact detection outside the bushing by UHF method. PD measurements with UHF method are carried out on the bushing. Then, the minimum energy method is used to extract time-difference-of-arrival (TDOA), and Chan algorithm is adopted to locate points of UHF signal radiation. High accuracy locating with a small error of 15 cm has been achieved. The contactless UHF method-based tests have demonstrated the effectiveness of online monitoring and locating of bushing PD.
引用
收藏
页码:684 / 692
页数:9
相关论文
共 28 条
  • [1] [Anonymous], 2015, P SBMO IEEE MTT S IN
  • [2] Computation of temperature distributions in transformer covers due to high crossing currents in bushing regions
    Cahue-Diaz, D.
    Maximov, S.
    Escarela-Perez, R.
    Olivares-Galvan, J. C.
    Alvarez-Ramirez, J.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 113 : 699 - 712
  • [3] A SIMPLE AND EFFICIENT ESTIMATOR FOR HYPERBOLIC LOCATION
    CHAN, YT
    HO, KC
    [J]. IEEE TRANSACTIONS ON SIGNAL PROCESSING, 1994, 42 (08) : 1905 - 1915
  • [4] Cheng YC, 2016, 2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P17, DOI 10.1109/EIC.2016.7548583
  • [5] Du B, 2020, TEMPERATURE DEPENDEN, P1, DOI [10.1049/hve.2019.0385, DOI 10.1049/HVE.2019.0385]
  • [6] Partial Discharges Pattern Recognition of Transformer Defect Model by LBP & HOG Features
    Firuzi, Keyvan
    Vakilian, Mehdi
    Phung, B. Toan
    Blackburn, Trevor R.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (02) : 542 - 550
  • [7] Measurement of Optical Signals Emitted by Surface Discharges on Bushing and Post Insulator
    Fracz, Pawel
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) : 1909 - 1914
  • [8] Hayt W.H., 2020, Engineering Electromagnetics| (SIE)
  • [9] Improving RF-Based Partial Discharge Localization via Machine Learning Ensemble Method
    Iorkyase, Ephraim Tersoo
    Tachtatzis, Christos
    Glover, Ian A.
    Lazaridis, Pavlos
    Upton, David
    Saeed, Bakhtiar
    Atkinson, Robert C.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1478 - 1489
  • [10] Sparsity-Aware Multi-Source TDOA Localization
    Jamali-Rad, Hadi
    Leus, Geert
    [J]. IEEE TRANSACTIONS ON SIGNAL PROCESSING, 2013, 61 (19) : 4874 - 4887