Grid Frequency Measurement through a PLHR Analysis Obtained from an ELF Magnetometer

被引:2
|
作者
Portillo, Francisco [1 ]
Alcayde, Alfredo [1 ]
Garcia, Rosa M. [1 ]
Novas, Nuria [1 ]
Antonio Gazquez, Jose [1 ]
Fernadez-Ros, Manuel [1 ]
机构
[1] Univ Almeria, Dept Engn, CeiA3, Almeria 04120, Spain
关键词
PLHR; frequency measurement; zero-crossing; FFT; LINE HARMONIC RADIATION; MAGNETIC-FIELDS; POWER; EXPOSURE; NETWORK; SYSTEMS; STATE; EARTH; EMF;
D O I
10.3390/s22082954
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The stability of the power grid's frequency is crucial for industrial, commercial, and domestic applications. The standard frequency in Europe's grid is 50 Hz and it must be as stable as possible; therefore, reliable measurement is essential to ensure that the frequency is within the limits defined in the standard EN 50160:2010. In this article, a method has been introduced for the measurement of the grid frequency through a power line harmonics radiation analysis. An extremely low-frequency magnetometer was developed with the specific purpose of monitoring, in real time, the electromagnetic field produced by electrical installations in the range from 0 to 2.2 kHz. Zero-crossing and Fast Fourier transform algorithms were applied to the output signal to calculate the grid frequency as a non-invasive method. As a final step, data for a complete month (May 2021) were compared with a commercial power quality analyzer connected to the main line to validate the results. The zero-crossing algorithm gave the best result on 3 May 2021, with a coefficient of determination (R-2) of 0.9801. Therefore, the indirect measurement of the grid frequency obtained through this analysis satisfactorily fits the grid frequency.
引用
收藏
页数:16
相关论文
共 5 条
  • [1] Photocurrent Measurement Through Frequency Domain Analysis
    Tiew, Chee-Chiang Derrick
    Kuang, Ye Chow
    2015 IEEE INTERNATIONAL INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE (I2MTC), 2015, : 440 - 445
  • [2] Analysis on power grid voltage frequency measurement method based on leakage current of capacitive equipment
    Du, L. (dulin@cqu.edu.cn), 1600, Science Press (38): : 1307 - 1312
  • [3] An Improved Frequency Measurement Method from the Digital PLL Structure for Single-Phase Grid-Connected PV Applications
    Yu, Byunggyu
    ELECTRONICS, 2018, 7 (08):
  • [4] Modeling and Measurement of Through-the-Earth Communication Based on ELF Magnetic Signals From Permanent Magnet Mechanical Antennas
    Zhang, Wenhou
    Cao, Zhenxin
    Wang, Xiaoyu
    Liu, Tong
    Wang, Jiacong
    IEEE SENSORS JOURNAL, 2025, 25 (01) : 1209 - 1215
  • [5] Frequency Support From a DC-Grid Offshore Wind Farm Connected Through an HVDC Link: A Communication-Free Approach
    Kou, Peng
    Liang, Deliang
    Wu, Zihao
    Ze, Qiji
    Gao, Lin
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2018, 33 (03) : 1297 - 1310