Sensitivity analysis of a PLC-based DSSS anti-islanding system in power distribution grids

被引:8
作者
Poluektov, Anton [1 ]
Pinomaa, Antti [1 ]
Romanenko, Aleksei [1 ]
Ahola, Jero [1 ]
Kosonen, Antti [1 ]
机构
[1] Lappeenranta Lahti Univ Technol LUT, LUT Sch Energy Syst, Lappeenranta, Finland
关键词
Direct-sequence spread spectrum; Distributed power generation; Islanding; Loss of mains; Power line communication; Sensitivity analysis; Software-defined radio; LINE COMMUNICATIONS; SMART GRIDS; COMMUNICATION; GENERATION; NOISE;
D O I
10.1016/j.ijepes.2019.06.022
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As smart grid applications, distributed generation, and microgrid technologies have become more widespread, new safety-related issues have arisen. Unintentional islanding is an example of a grid fault that may result in damage to electrical equipment and severe personal injuries. In this paper, an anti-islanding system employing power line communication (PLC) and direct-sequence spread spectrum (DSSS) modulation implemented with software-defined radios for continuous signaling is tested in a laboratory test setup. A concept of a fault detection algorithm is evaluated. A DSSS sensitivity analysis is carried out to investigate system's performance against variation of a signal-to-noise ratio, and define optimal DSSS settings. The results of the analysis are interpreted, and conclusions are drawn. A transformer bypassing scheme allowing to increase the fault detection speed and throughput is introduced and tested, and the conditions of applicability are described. As a result of the study, recommendations for the system development are presented.
引用
收藏
页码:739 / 747
页数:9
相关论文
共 49 条
[21]   Power Line Channel Characteristics and Their Effect on Communication System Design [J].
Goetz, Matthias ;
Rapp, Manuel ;
Dostert, Klaus .
IEEE COMMUNICATIONS MAGAZINE, 2004, 42 (04) :78-86
[22]   Islanding-Aware Robust Energy Management for Microgrids [J].
Guo, Yuanxiong ;
Zhao, Chaoyue .
IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (02) :1301-1309
[23]   Hybrid Islanding Detection in Microgrid With Multiple Connection Points to Smart Grids Using Fuzzy-Neural Network [J].
Kermany, Saman Darvish ;
Joorabian, Mahmood ;
Deilami, Sara ;
Masoum, Mohammad A. S. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (04) :2640-2651
[24]  
Kikkert C.J., 2011, 2011 IEEE PES Innovative Smart Grid Technologies, P1, DOI [DOI 10.1109/ISGT-ASIA.2011.6167075, 10.1109/ISGT-Asia.2011.6167075]
[25]  
Kim I., 2015, 2015 IEEE International Magnetics Conference (INTERMAG), DOI 10.1109/INTMAG.2015.7157583
[26]   Comparison of signal coupling methods for power line communication between a motor and an inverter [J].
Kosonen, A. ;
Ahola, J. .
IET ELECTRIC POWER APPLICATIONS, 2010, 4 (06) :431-440
[27]   Advanced Islanding Detection Functionality for Future Electricity Distribution Networks [J].
Laaksonen, H. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) :2056-2064
[28]   A review of islanding detection methods for microgrid [J].
Li, Canbing ;
Cao, Chi ;
Cao, Yijia ;
Kuang, Yonghong ;
Zeng, Long ;
Fang, Baling .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 35 :211-220
[29]   Experimental Performance of an Islanding Detection Scheme Based on Modal Components [J].
Makwana, Yogesh M. ;
Bhalja, Bhavesh R. .
IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (01) :1025-1035
[30]   Islanding Detection for Inverter-Based Distributed Generation Using Support Vector Machine Method [J].
Matic-Cuka, Biljana ;
Kezunovic, Mladen .
IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (06) :2676-2686