Sensitivity analysis of a PLC-based DSSS anti-islanding system in power distribution grids

被引:8
作者
Poluektov, Anton [1 ]
Pinomaa, Antti [1 ]
Romanenko, Aleksei [1 ]
Ahola, Jero [1 ]
Kosonen, Antti [1 ]
机构
[1] Lappeenranta Lahti Univ Technol LUT, LUT Sch Energy Syst, Lappeenranta, Finland
关键词
Direct-sequence spread spectrum; Distributed power generation; Islanding; Loss of mains; Power line communication; Sensitivity analysis; Software-defined radio; LINE COMMUNICATIONS; SMART GRIDS; COMMUNICATION; GENERATION; NOISE;
D O I
10.1016/j.ijepes.2019.06.022
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As smart grid applications, distributed generation, and microgrid technologies have become more widespread, new safety-related issues have arisen. Unintentional islanding is an example of a grid fault that may result in damage to electrical equipment and severe personal injuries. In this paper, an anti-islanding system employing power line communication (PLC) and direct-sequence spread spectrum (DSSS) modulation implemented with software-defined radios for continuous signaling is tested in a laboratory test setup. A concept of a fault detection algorithm is evaluated. A DSSS sensitivity analysis is carried out to investigate system's performance against variation of a signal-to-noise ratio, and define optimal DSSS settings. The results of the analysis are interpreted, and conclusions are drawn. A transformer bypassing scheme allowing to increase the fault detection speed and throughput is introduced and tested, and the conditions of applicability are described. As a result of the study, recommendations for the system development are presented.
引用
收藏
页码:739 / 747
页数:9
相关论文
共 49 条
[1]   A passive islanding detection strategy for multi-distributed generations [J].
Abd-Elkader, Ahmad G. ;
Saleh, Saber M. ;
Eiteba, M. B. Magdi .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 99 :146-155
[2]   Broadband power-line communications: The channel capacity analysis [J].
Anatory, Justinian ;
Theethayi, Nelson ;
Thottappillil, Rajeev ;
Kissaka, Mussa M. ;
Mvungi, Nerey H. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) :164-170
[3]   Reliable Generator Islanding Detection for Industrial Power Consumers With On-Site Generation [J].
Anne, RadhaKiranMaye ;
Basha, Faridul Katha ;
Palaniappan, Ramanathan ;
Oliver, Kent L. ;
Thompson, Michael J. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2016, 52 (01) :668-676
[4]  
[Anonymous], 2018 IEEE PES INN SM
[5]  
[Anonymous], ELECT POWER ENERGY S
[6]  
[Anonymous], TITL 47 CFR 15
[7]  
[Anonymous], THESIS
[8]  
[Anonymous], 2014, 1547 IEEE
[9]  
[Anonymous], G3 PLC PHYS LAYER SP
[10]  
[Anonymous], 2000, 9292000 IEEE